York DY 048 User Manual

Page 23

Advertising
background image

343615-YTG-B-0308

Johnson Controls Unitary Products

23

060

(5.0)

208-1-60 28.8 145.0

45.0

2.3

7.6

10.0

None

-

-

-

55.9

60

E05

4.0

1

19.2

55.9

60

E07

5.6

1

26.9

55.9

60

E10

8.0

1

38.5

70.1

80

E15

11.9

2

57.2

93.5

100

E20

15.9

2

76.4

117.6

125

E30

22.2

2

106.7

155.4

175

230-1-60 28.8 145.0

45.0

2.3

7.6

10.0

None

-

-

-

55.9

60

E05

5.3

1

23.0

55.9

60

E07

7.5

1

32.6

61.1

70

E10

10.6

1

46.1

77.2

80

E15

15.9

2

69.1

104.8

110

E20

21.2

2

92.2

132.4

150

E30

29.6

2

128.7

176.2

200

208-3-60 17.3 123.0

27.0

2.3

7.6

10.0

None

-

-

-

41.5

45

E05

4.0

1

11.1

41.5

45

E07

5.6

1

15.5

41.5

45

E10

8.0

1

22.2

49.8

50

E15

11.9

2

33.0

63.3

70

E20

15.9

2

44.1

77.2

80

E30

22.2

2

61.6

99.0

100

230-3-60 17.3 123.0

27.0

2.3

7.6

10.0

None

-

-

-

41.5

45

E05

5.3

1

13.3

41.5

45

E07

7.5

1

18.8

44.6

45

E10

10.6

1

26.6

53.9

60

E15

15.9

2

39.9

69.8

70

E20

21.2

2

53.2

85.7

90

E30

29.6

2

74.3

111.0

125

460-3-60

9.6

70.0

15.0

1.3

7.6

5.0

None

-

-

-

22.1

25

E07

6.8

1

8.5

22.1

25

E10

10.1

1

12.7

26.2

25

E15

13.6

2

17.1

31.4

30

E20

19.5

2

24.5

40.3

40

E30

28.8

2

36.1

54.3

60

575-3-60

7.4

53.0

11.5

1.3

7.6

4.0

None

-

-

-

17.3

20

E10

10.6

1

10.6

21.5

20

E15

15.9

1

16.0

27.9

30

E20

21.2

2

21.3

34.3

35

E30

30.4

2

30.5

45.4

45

1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.

TABLE 24: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET (CONT)

Size

(Tons)

Volt

Compressors

(each)

OD Fan

Motors

(each)

Supply
Blower

Motor

Pwr

Conv

Outlet

Electric Heat Option

MCA

1

(Amps)

Max

Fuse

2

/

Breaker

3

Size

(Amps)

RLA

LRA

MCC

FLA

FLA

FLA

Model

kW

Stages

Amps

Advertising