York DY 048 User Manual

Page 21

Advertising
background image

343615-YTG-B-0308

Johnson Controls Unitary Products

21

060

(5.0)

208-1-60 28.8 145.0

45.0

2.3

7.6

0.0

None

-

-

-

45.9

50

E05

4.0

1

19.2

45.9

50

E07

5.6

1

26.9

45.9

50

E10

8.0

1

38.5

57.6

60

E15

11.9

2

57.2

81.0

90

E20

15.9

2

76.4

105.1

110

E30

22.2

2

106.7

142.9

150

230-1-60 28.8 145.0

45.0

2.3

7.6

0.0

None

-

-

-

45.9

50

E05

5.3

1

23.0

45.9

50

E07

7.5

1

32.6

48.6

50

E10

10.6

1

46.1

64.7

70

E15

15.9

2

69.1

92.3

100

E20

21.2

2

92.2

119.9

125

E30

29.6

2

128.7

163.7

175

208-3-60 17.3 123.0

27.0

2.3

7.6

0.0

None

-

-

-

31.5

35

E05

4.0

1

11.1

31.5

35

E07

5.6

1

15.5

31.5

35

E10

8.0

1

22.2

37.3

40

E15

11.9

2

33.0

50.8

60

E20

15.9

2

44.1

64.7

70

E30

22.2

2

61.6

86.5

90

230-3-60 17.3 123.0

27.0

2.3

7.6

0.0

None

-

-

-

31.5

35

E05

5.3

1

13.3

31.5

35

E07

7.5

1

18.8

32.1

35

E10

10.6

1

26.6

41.4

45

E15

15.9

2

39.9

57.3

60

E20

21.2

2

53.2

73.2

80

E30

29.6

2

74.3

98.5

100

460-3-60

9.6

70.0

15.0

1.3

7.6

0.0

None

-

-

-

17.1

20

E07

6.8

1

8.5

17.1

20

E10

10.1

1

12.7

19.9

20

E15

13.6

2

17.1

25.2

25

E20

19.5

2

24.5

34.1

35

E30

28.8

2

36.1

48.1

50

575-3-60

7.4

53.0

11.5

1.3

7.6

0.0

None

-

-

-

13.3

15

E10

10.6

1

10.6

16.5

20

E15

15.9

1

16.0

22.9

25

E20

21.2

2

21.3

29.3

30

E30

30.4

2

30.5

40.4

40

1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.

TABLE 23: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET (CONT)

Size

(Tons)

Volt

Compressors

(each)

OD Fan

Motors

(each)

Supply
Blower

Motor

Pwr

Conv

Outlet

Electric Heat Option

MCA

1

(Amps)

Max

Fuse

2

/

Breaker

3

Size

(Amps)

RLA

LRA

MCC

FLA

FLA

FLA

Model

kW

Stages

Amps