Appendix, Page 131 – Xantrex Technology 120 VAC/60 User Manual

Page 139

Advertising
background image

APPENDIX

2001 Xantrex Technology, Inc.

5916 - 195th Street N. E.
Arlington, WA 98223

Telephone: 360/435-8826

Fax: 360/435-2229

www.traceengineering.com

SW Series Inverter/Charger

Part No. 2031-5

Rev. C: February 2001

Page

131

Note: Sizes shown are for the conductor – do not include any insulation when determining your wire
size.

Figure 40, AWG Wire Size

Table 11, Minimum Recommended Battery Cable Size vs. Cable Length

INVERTER

MODEL

TYPICAL

DC

AMPS

1

NEC

AMPS

2

1 TO 3 FEET

ONE WAY

3 TO 5 FT

ONE WAY

5 TO 10 FT

ONE WAY

SW2512

267 Amps

334 Amps

#4/0 AWG/107 mm

2

#4/0 AWG/107 mm

2

Not Recommended

SW2612E

278 Amps

348 Amps

#4/0 AWG/107 mm

2

#4/0 AWG/107 mm

2

Not Recommended

SW3024E or J

160 Amps

201 Amps

#4/0 AWG/107 mm

2

#4/0 AWG/107 mm

2

#4/0 AWG/107 mm

2

SW4024 or W, K

214 Amps

267 Amps

#4/0 AWG/107 mm

2

#4/0 AWG/107 mm

2

#4/0 AWG/107 mm

2

SW3048E or J

80 Amps

100 Amps

#2/0 AWG/67.4 mm

2

#2/0 AWG/67.4 mm

2

#4/0 AWG/107 mm

2

SW4048 or K

107 Amps

134 Amps

#2/0 AWG/67.4 mm

2

#2/0 AWG/67.4 mm

2

#4/0 AWG/107 mm

2

SW4548E or A

120 Amps

150 Amps

#2/0 AWG/67.4 mm

2

#2/0 AWG/67.4 mm

2

#4/0 AWG/107 mm

2

SW5548

147 Amps

184 Amps

#4/0 AWG/107 mm

2

#4/0 AWG/107 mm

2

#4/0 AWG/107 mm

2

1

TYPICAL DC AMPS is based on Low Battery Voltage with an efficiency of 85%.

2

NEC AMPS is based on Low Battery Voltage, an efficiency of 85%, and a 125% NEC de-rating.

Table 12, Battery Cable to Maximum Breaker/Fuse Size

CABLE SIZE

REQUIRED

RATING IN

CONDUIT

MAXIMUM

BREAKER SIZE

RATING IN

“FREE AIR”

MAXIMUM

FUSE SIZE

#2 AWG

115 amps

125 amps*

170 amps

175 amps*

#2/0 (00) AWG

175 amps

175 amps

265 amps

300 amps*

#4/0 (0000) AWG

230 amps

250 amps*

360 amps

400 amps*

* The NEC allows rounding up to the next standard fuse size from the cable rating, i.e. 150-amp cable size
rounds up to a standard 175-amp size.

The term "free air" is defined by the NEC as cabling that is not enclosed in conduit or a raceway. Cables
enclosed in raceways or conduits have substantially lower continuous current carrying ability due to
heating factors.

3/0

.475

4/0

.530

250 MCM

.580

300 MCM

.635

350 MCM

.690

400 MCM

.730

500 MCM

.820

1

.335

1/0

.380

2/0

.420

12

.072

10

.115

8

.146

6

.184

4

.235

3

.281

2

.295

14

.073

SIZE

DIAMETE

R

SIZE

DIAMETE

R

Advertising