Menu system, Page 47 battery charging (10) menu heading – Xantrex Technology 120 VAC/60 User Manual

Page 55

Advertising
background image

MENU SYSTEM

2001 Xantrex Technology, Inc.

5916 - 195th Street N. E.
Arlington, WA 98223

Telephone: 360/435-8826

Fax: 360/435-2229

www.traceengineering.com

SW Series Inverter/Charger

Part No. 2031-5

Rev. C: February 2001

Page

47

BATTERY CHARGING (10) MENU HEADING

Note: See the battery section of this manual for recommended setting for different battery types.

Set Bulk
volts DC

14.4

Set Bulk
volts DC

28.8

Set Bulk
volts DC

57.6

12 VDC models

Range: 10.0 to 16.0

24 VDC models

Range: 20.0 to 32.0

48 VDC models

Range: 40.0 to 64.0

Sets the voltage level that will be maintained during the first and second stage of the charging process.
This will be the maximum voltage at which the batteries will be charged. This setting will be
compensated for the battery temperature if the BTS sensor is installed.

Set Absorption
time h:m

02:00

All models

Range: 00:00 to 23:50

Sets the time period that the batteries will be held near the SET BULK VOLTS DC level for the second
stage of the battery charging process, this ensures that the battery is well charged. If the automatic
generator control system is used, the generator will turn off when the batteries have been held near the
SET BULK VOLTS DC setting until the ABSORPTION TIME period has elapsed. This time is an
accumulating or up/down type timer - it counts up while the voltage is near the BULK setting and counts
back down if the voltage drops. This makes the process more reliable and predictable. If the system
designer wants to minimize generator operation, a shorter time may be used. If the system designer wants
to ensure that the batteries are fully charged before stopping the charging process, then a longer setting
may be used. If the ABSORPTION TIME is set to zero (00:00) the unit will not provide any absorption
charge time and go straight to the float charge stage after reaching near the BULK voltage setting.

Set Float
volts DC

13.4

Set Float
volts DC

26.8

Set Float
volts DC

53.6

12 VDC models

Range: 10.0 to 16.0

24 VDC models

Range: 20.0 to 32.0

48 VDC models

Range: 40.0 to 64.0

Sets the voltage level that will be maintained at the final stage of the charging process. This is important for
systems which are connected to utility power since the battery charger will often be in this stage most of the
time. This setting will be compensated for the battery temperature if the BTS sensor is installed.

Set Equalize
volts DC

14.4

Set Equalize
volts DC

28.8

Set Equalize
volts DC

57.6

12 VDC models

Range: 10.0 to 16.0

24 VDC models

Range: 20.0 to 32.0

48 VDC models

Range: 40.0 to 64.0

Sets the voltage level that the batteries will be limited to during the equalization process. This will be the
maximum voltage at which the batteries will be charged. This setting will be compensated for the
battery temperature if the BTS sensor is installed.

Set Equalize
time h:m

02:00

All models

Range: 00:00 to 23:50

Sets the amount of time battery voltage must exceed the BULK VOLTS DC setting before the equalization
process is considered to be completed. If the automatic generator control system is used; it will turn off the
generator when this timer has reached its setting, and return the cursor from the EQ to the AUTO position.
This time is an accumulating or up/down type timer - it counts up while the voltage is above the BULK
setting and counts back down if the voltage drops below the BULK setting for a period of time.

Advertising