Controls, indicators and components, Page 13 internal components and indicators – Xantrex Technology 120 VAC/60 User Manual

Page 21

Advertising
background image

CONTROLS, INDICATORS AND COMPONENTS

2001 Xantrex Technology, Inc.

5916 - 195th Street N. E.
Arlington, WA 98223

Telephone: 360/435-8826

Fax: 360/435-2229

www.traceengineering.com

SW Series Inverter/Charger

Part No. 2031-5

Rev. C: February 2001

Page

13

INTERNAL COMPONENTS AND INDICATORS

Additional components and indicators are located behind three removable AC Access Panels located on
the AC Side of the unit. They include the AC Terminal Block, BTS Connector, three LED indicators and
the Aux and Gen Control Relay Connectors.

Figure 5, Internal Components and Indicators

LED INDICATORS

Three LED indicators allow visual indication of operation of the RY7, RY8 and AC1 relays.

RY7 (Yellow) LED

Allows visual indication of relay RY7 operation. During the automatic generator control sequence, the
LED will be on to show that RY7 is closed (engaged) from the N.O. to the COM contacts, and will be
off when RY7 is opened (disengaged).

RY8 (Green) LED

Allows visual indication of relay RY8 operation. During the automatic generator control sequence, the
LED will be on to show that RY8 is closed (engaged) from the N.O. to the COM contacts, and will be
off when RY8 is opened (disengaged).

AC1 RELAY (Red) LED

Allows visual indication of AC1 relay operation. The LED will be on when the AC1 relay is closed
(engaged). This LED along with the test-jumper adjacent to the LED is used by utilities to perform
voltage and frequency tests to qualify the SW Series Inverter/Charger for line-tie applications.

BTS PORT

The battery temperature sensor (BTS) can be connected (plugged in) at the RJ-11 four-conductor
connector, located on the AC Circuit Board. The BTS provides information that enables the three-stage
standby battery charger to “fine tune” the battery charge voltages for better charging performance, greater
efficiency and longer battery life.

AC TERMINAL BLOCK

A six position terminal block is provided to make the AC connections. The terminal block is located on the
AC Circuit Board. The terminal block is used to hardwire all AC input and output connections.

RY7 (Yellow)

LED

RY8 (Green)

LED

AC1 Relay
(Red) LED

BTS

Connector

AC

Terminal Block

AC

Safety Ground

Aux and Gen Control

Relay Connectors

Advertising