Typical field control wiring diagram, 10 additional static pressure resistance, 1/2 - 3-1/2 ton (dna030 - 042) – York AFFINITY 292443-XTG-D-0508 User Manual

Page 14: 11 additional static pressure resistance, 4 - 5 ton (dna048 - 060), Programmable thermostat only, Thermostat unit terminal strip, 24 volt transformer

Advertising
background image

292443-XTG-D-0508

14

Johnson Controls Unitary Products

FIGURE 3 - TYPICAL FIELD CONTROL WIRING DIAGRAM

TABLE 10: ADDITIONAL STATIC PRESSURE RESISTANCE 2-1/2 - 3-1/2 TON (DNA030 - 042)

1

DESCRIPTION

RESISTANCE, IWG

CFM

500

600

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

1,600

1,700

1,800

1,900

2,000

WET EVAPORATOR COIL

.01

.01

.01

.02

.03

.04

.05

.06

.07

.08

.09

.09

-

-

-

-

ECONOMIZER

2

.00

.00

.00

.01

.01

.01

.01

.02

.03

.04

.05

.06

-

-

-

-

FILTER FRAME KIT

.01

.02

.04

.06

.08

.10

.13

.16

.17

.18

.19

.20

-

-

-

-

1. Deduct these resistance values from the available external static pressure shown in Tables 8 and 9.
2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air

duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 11: ADDITIONAL STATIC PRESSURE RESISTANCE 4 - 5 TON (DNA048 - 060)

1

DESCRIPTION

RESISTANCE, IWG

CFM

500

600

700

800

900

1,000

1,100

1,200

1,300

1,400

1,500

1,600

1,700

1,800

1,900

2,000

WET EVAPORATOR COIL

-

-

-

-

-

-

-

.03

.04

.05

.06

.07

.07

.08

.09

.09

ECONOMIZER

2

-

-

-

-

-

-

-

.02

.02

.03

.03

.04

.04

.04

.05

.05

FILTER FRAME KIT

-

-

-

-

-

-

-

.04

.05

.05

.06

.07

.08

.09

.10

.11

1. Deduct these resistance values from the available external static pressure shown in Table 8 and 9.
2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct

system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.

R

G

W

R

G

C

Y

Y

W

C

PROGRAMMABLE

THERMOSTAT ONLY

**

** = Minimum wire size of 18 AWG

wire should be used for all
field installed 24 volt wire.

THERMOSTAT

UNIT TERMINAL STRIP

NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.35
AMPS FOR ALL MODELS.

24 VOLT
TRANSFORMER