Table 12: electrical data, Typical field power wiring diagram, 12 electrical data – York AFFINITY 292443-XTG-D-0508 User Manual

Page 15

Advertising
background image

292443-XTG-D-0508

Johnson Controls Unitary Products

15

FIGURE 4 - TYPICAL FIELD POWER WIRING DIAGRAM

CONTACTOR

FIELD-SUPPLIED

DISCONNECT

SINGLE
PHASE
POWER
SUPPLY

GROUND

LUG

REFER TO ELECTRICAL
DATA TABLES TO SIZE
THE DISCONNECT

CONTACTOR

GROUND

LUG

FIELD-SUPPLIED

DISCONNECT

THREE
PHASE
POWER
SUPPLY

REFER TO ELECTRICAL
DATA TABLES TO SIZE
THE DISCONNECT

TABLE 12: ELECTRICAL DATA

MODEL

DNA

POWER

SUPPLY

VOLTAGE

LIMITATIONS

1

COMPRESSOR

COND.

FAN

MOTOR,

FLA

SUPPLY

AIR

BLOWER

MOTOR

FLA

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,

AMPS

2

MAX.

HACR

BREAKER

SIZE,

AMPS

UNIT

POWER

FACTOR

TRANSFORMER

SIZE (VA)

MIN.

MAX.

RLA

LRA

030

208/230-1-60

187

253

14.7

73

1.1

2.2

21.7

30

30

0.96

40

036

208/230-1-60

187

253

17.3

94

1.1

3.5

26.2

35

35

0.96

40

036

208/230-3-60

187

253

10.9

78

1.1

3.5

18.2

25

25

0.96

75

036

460-3-60

414

504

5.8

40

0.6

1.8

9.6

15

15

0.96

75

042

208/230-1-60

187

253

15.4

86

1.1

3.5

23.9

30

30

0.96

40

042

208/230-3-60

187

253

11.5

88

1.1

3.5

19

25

25

0.96

75

042

460-3-60

414

504

5.8

42

0.6

1.8

9.7

15

15

0.96

75

048

208/230-1-60

187

253

24.4

140

1.3

7

38.8

50

50

0.96

40

048

208/230-3-60

187

253

14.1

105

1.3

7

25.9

35

35

0.96

75

048

460-3-60

414

504

7.1

55

0.7

3.5

13.1

20

20

0.96

75

060

208/230-1-60

187

253

28.9

175

1.3

7

44.4

60

60

0.96

40

060

208/230-3-60

187

253

15.5

125

1.3

7

29.5

40

40

0.96

75

060

460-3-60

414

504

8.9

66.5

0.7

3.5

15.4

20

20

0.96

75

1. Utilization range “A” in accordance with ARI Standard 110.
2. Dual element, time delay type.