Table 13: unit dimensions front, Table 14: unit minimum clearances, Unit dimensions - front – York AFFINITY 292443-XTG-D-0508 User Manual

Page 16: 13 unit dimensions front, 14 unit minimum clearances, Figure 5 - unit dimensions - front

Advertising
background image

292443-XTG-D-0508

16

Johnson Controls Unitary Products

FIGURE 5 - UNIT DIMENSIONS - FRONT

3-3/4

2-1/2

47-1/4

1-1/2

2-5/8

3-1/3

5-3/8

11

12-3/4

49-1/8

A

2-3/8

VENT AIR OUTLET HOOD

BLOWER SERVICE
ACCESS COMPARTMENT
PANEL

GAS SUPPLY 1-1/4" DIA.
HOLE (1/2" NPTI
CONNECTION)

UNIT CONDENSATE
CONNECTION 3/4" NPTI
(TRAP RECOMMENDED)

B

HIGH VOLTAGE
CONN. 1-3/8" DIA.
KNOCKOUT

HIGH VOLTAGE
CONN. 7/8" DIA.
KNOCKOUT

GAS SUPPLY 1-1/4" DIA.
KNOCKOUT (1/2" NPTI
CONNECTION)

LOW VOLTAGE CONN.
1-3/8" DIA. KNOCKOUT
X 7/8" HOLE

CONDENSER COIL

REFRIGERANT
CONNECTIONS

COMBUSTION AIR
INLET LOUVERS

FRONT

GAS/ELECTRIC CONTROL

SERVICE ACCESS

COMPARTMENT PANEL

(OVERALL)

(OVERALL)

TABLE 13: UNIT DIMENSIONS FRONT

UNIT SIZE

DIMENSION

“A”

“B”

030 thru 042

33-1/2

18-1/4

048 and 060

41-1/2

23-1/8

TABLE 14: UNIT MINIMUM CLEARANCES

1

2

1. A 1” clearance must be provided between any combus-

tible material and the supply air ductwork.

2. The products of combustion must not be allowed to

accumulate within a confined space and recirculate.

CLEARANCES

FRONT

36”

REAR

0”

LEFT SIDE (Filter-Access)

24”

RIGHT SIDE

12”

BELOW UNIT

3

3. Units may be installed on combustible floors made from

wood or class A, B, or C roof covering material.

0”

ABOVE UNIT

4

4. Units must be installed outdoors. Overhanging struc-

tures or shrubs should not obstruct condenser air dis-
charge outlet.

36” (For Condenser Air Discharge