Grounding series-stacked inverters, To ground series-stacked inverters, Grounding series-stacked inverters –3 – Xantrex Technology power Inverter Stacking User Manual

Page 21: Figure 2-2, Dc grounding of series-stacked inverters –3

Advertising
background image

DC Wiring

975-0059-01-01 Rev A

2–3

Grounding Series-stacked Inverters

To ground series-stacked inverters:

1.

Connect the ground bond in the DC disconnect between the inverters and the
batteries to the primary grounding electrode, in accordance with local and
national electrical codes.

2.

Connect an appropriately sized ground wire from the chassis bonding ground
lug on the L1 inverter DC end to the ground bond inside the DC disconnect.

3.

Connect a second appropriately sized ground wire from the chassis bonding
ground lug on the L2 inverter DC end to a different terminal in the ground
bond inside the DC disconnect.

Figure 2-2 DC Grounding of Series-stacked Inverters

GROUND

SHUNT &

NEGATIVE BUS

DC

DISCONNECT

01A Inverter

OFF SRCH ON CHG

R e s e t D e fa u lts

C o n tr a s t

O N /O F F

M E N U

M E N U

HE A D IN G S

M E N U

IT E M S

S E T

P O IN T S

INV

GEN

I nver t er Cont r ol M odul e

G R ID T IE

IN V ER T

A C 2

F L O A T

S T A T U S

E R R O R

B U L K

A C 1

xantrex

+

xantrex

S i ne Wave P l us I nverter/ Charger

Chassis Bonding

Ground Lug

L1 Inverter

01A Inverter
OFF SRCH ON CHG

R e s e t D e fa u lts

C o n tr a s t

O N /O F F

M E N U

M E N U

H E A D IN G S

M E N U
IT E M S

S E T

P O IN T S

INV

GEN

I nver t er Cont r ol M odule

G R ID T IE

IN V ER T

A C 2

F L O A T S T A T U S

E R R O R

B U L K

A C 1

xantrex

+

xantrex

S i ne Wave P l us Inverter/ Charger

L2 Inverter

To primary

Earth/ground

connections

ON

OFF

ON

OFF

ON

OFF

Chassis Bonding

Ground Lug

Advertising