Automatic generator equalize charging, Manual equalize charging, Important – Xantrex Technology power Inverter Stacking User Manual

Page 41

Advertising
background image

Setting Changes

975-0059-01-01 Rev A

3–5

Automatic Generator Equalize Charging

If the inverters are set to automatically charge the batteries using the generator, the
equalize process will begin during the next, automatically started, generator run
period. When

the equalizing process has completed, the generator automatically

stops and the cursor returns to the OFF position in the 01B EQ C

HARGE

menu

item on the generator-controlling inverter. The non-generator-controlling inverter
must be set from EQ to OFF from the 01B EQ C

HARGE

menu item or it will start

another equalize charge the next time the generator is started.

Manual Equalize Charging

If the batteries were equalized using a manually started generator or from the
utility grid, the F

LOAT

LED illuminates, indicating the equalization process is

complete. Set the cursor to OFF on both inverters under the 01B EQ C

HARGE

menu item when the equalization process is complete.

Important:

If using multiple battery temperature sensors (BTS) ensure they are all

connected to the same location (battery).