Ac wiring - specific, Off-grid ac wiring for sine wave plus inverters, Grounding – Xantrex Technology power Inverter Stacking User Manual

Page 26: Connect ground (green) wires, Neutral bonds, Connect neutral (white) wires, Inverter to ac distribution panel, Connect a hot wire, Ac wiring - specific –8, Off-grid ac wiring for sine wave plus inverters –8

Advertising
background image

Installation

2–8

975-0059-01-01 Rev A

AC Wiring - Specific

The following AC connections are specific to installing the Sine Wave Plus
Inverter/chargers in a series-stacked configuration for off-grid and on-grid
applications.

Off-Grid AC Wiring for Sine Wave Plus Inverters

The following steps are illustrated in

Figure 2-4

.

To connect the AC wiring for an off-grid application using Sine Wave Plus
Inverters:

Grounding

1.

Connect G

ROUND

(green) wires:

a) from the primary earth/ground to the AC distribution panel,

b) from the L1 inverter AC ground bar to the inverter panel ground bar,

c) from the L2 inverter AC ground bar to the inverter panel ground bar.

Neutral Bonds

2.

Connect N

EUTRAL

(white) wires:

a) from the N

EUTRAL

bus in the inverter panel, to the ground bar in the

inverter panel, (Neutral-to-Ground Bond),

b) from the L1 inverter N

EUTRAL

O

UT

terminal, to the L2 inverter N

EUTRAL

2 terminal. (Inverter-to-inverter neutral bond),

c) from the L2 inverter N

EUTRAL

O

UT

terminal to the inverter panel

N

EUTRAL

bus. (Common neutral bond in inverter panel).

Inverter to AC
Distribution Panel

3.

Connect a HOT wire:

a) (black) from the L1 inverter AC H

OT

O

UTPUT

(120 Vac) to the inverter

panel L1 terminal,

b) (red) from the L2 inverter AC H

OT

O

UTPUT

(120 Vac) to the inverter

panel L2 terminal.

4.

Torque all inverter terminal block connections to 25 inch-pounds.