2-4

975-0343-01-01

Battery Charger function illuminates, reverse polarity has
been detected. Correct polarity must be established
before proceeding. Go back to Step 3.

5. The Charge Rate indicator light will blink. Select the

suitable charging current for your battery (see Table 2-2
on page 2-5) by toggling the Charge Rate push button
located below the indicator light. If the charging current
is not selected within 10 seconds, the unit will set to a
default charge rate of 2 A.

6. The Charging Status indicator light on the Battery

Charger function section will blink and the fully-
automatic charging sequence begins.

7. During charging, the charging current can be set to a

different charge rate or terminated at any time by
toggling the Charge Rate push button.

8. During charging, you can toggle the Display Selection

push button to show either the charging voltage or the
charging current on the Digital Display.

9. When the charging process is complete, the Charging

Status indicator light on the Battery Charger function
section changes from blinking to solid.
A 24-hour timer is built into the unit to avoid battery
overcharging.
The charger will automatically recharge the battery if the
charge current rises above the threshold specified in
Table 2-1.

Table 2-1 Duracell® 15 AMP Charger

Charging Rate Threshold

2 A

0.6

8 A

1.5

15 A

2.0

0

2

8

15

Duracell® 15 AMP Charger

Duracell_Charger15.book Page 4 Friday, June 15, 2007 2:34 PM