Installation and Startup

CAUTION:

If the UPS does not have an automatic protection device against current backfeed, install an

external isolating device. After the device is installed, you must add a warning label with the following
wording or the equivalent on the external AC contactor: RISK OF VOLTAGE BACKFEED. Isolate the UPS before
operating on this circuit, then check for hazardous voltage between all terminals.

External Distribution Panel

UPS

L/L1

L/L1

N/L2

N/L2

Legend

Coil Remote Switch
Magneto-Thermal Input
Main Switch

AC Contactor

Neutral/L2
L1 Line Input

B
Q

T
N/L2
L/L1

B

Q

T

The following table lists backfeed protection devices (AC contactors) that can be used as an external

isolating device for backfeed protection. Only use AC contactors listed in the table.

Manufacturer

Type

Rating

ABB France (E12527)

A75-30

220–240 Vac, 105A

25 HP at 208V, 30HP at

240V

Tianshui 213 Electrical Apparatus Co., Ltd.

(E203071)

(alternative)

GSC1(CJX4-d)-6511

220–240 Vac, 68A

25 HP

Tianshui 213 Electrical Apparatus Co., Ltd.

(E203071)

(alternative)

GSC1(CJX4-d)-8011

220–240 Vac, 80A

30 HP

NOTE:

Although the UPS does not contain anti-backfeed (ABF) relays, some backfeed protection is provided.

For example, if some components are damaged in battery mode, the output voltage may feed back to the input.
In this case, a current transformer (CT) is used to detect the bypass current feedback voltage. If a current
backfeed fault condition is detected, the UPS will terminate the inverter output to avoid the personal injury.