Operation

Summary of Operational Limits

References to the specifications indicate that the absolute limit is

determined by the specific configuration of the Model 430 Programmer

purchased.

Table 3-7.

Summary of Model 430 Programmer Limits and Defaults

Model 430 Setting (Units)

Absolute Limits

Default Setting

a

a. Unless preset by factory.

Min Output Voltage (V)

0.000 to

-

20.000

-6.000

Max Output Voltage (V)

0.001 to +20.000

6.000

Min Output Current (A)

see table on

page 8

-125.000

Max Output Current (A)

see table on

page 8

125.000

V-V Mode Input Range (V)

-

10.000 to +10.000

-10.000 to +10.000

Stability Setting (%)

0.0 to 100.0

0.0

Coil Constant (kG/A)

0.001 to 999.99999

1.0

PSwitch Current (mA)

0.0 to 125.0

10.0

PSwitch Heated Time (sec)

5 to 120

20

PSwitch Cooled Time (sec)

5 to 3600

20

PSwitch Power Supply
Ramp Rate (A/sec)

same as min and max ramp

(see table on

page 8

)

10

PSwitch Cooling Gain

0.0 to 100.0

0.0

Magnet Current Rating (A)

+/-0.001 to

+/-

9999.9999999999

80.000

Current Limit (A)

Min Output Current

and

Max Output Current

80.000

Display Brightness (%)

25, 50, 75, 100

100

Voltage Limit (V)

0.001

and

Max Output Voltage

2.000

Ramp Rate (A/sec)

see table on

page 8

0.100

Target Current (A)

Current Limit

5.000

Advertising