installation checklist

1. Inspect components

Required hardware

AcquiSuite DR™ H8822-1 server (required)

•

Data connection (ethernet or phone line).

•

Ethernet Cat 5 standard or crossover cable (required for LAN or direct

•

laptop-to-AcquiSuite DR connection); or
Phone line and cord (required for modem connection)

•

Optional hardware

Analog sensors for temperature, humidity, etc.

•

Pulse output transducers for measuring gas, electricity, water, etc. from

•

existing meters and sensors.
Additional Modbus RTU devices power meters (e.g., Veris Enercept, PML

•

Ion, etc)

2. Choose a connection method

For LAN installations only:

Ethernet 10/100Mbit connection point (hub or switch)

•

IP address and Netmask (check with system administrator)

•

Gateway address (check with system administrator)

•

DNS server address (check with system administrator)

•

HTTP Proxy address (optional), may be required if the AcquiSuite DR is

•

behind a firewall (check with system administrator)

For dialout installations only (AcquiSuite DR initiates a phone call to your ISP or
modem server):

Phone line with dialtone. May be shared with other devices such as a fax

•

machine
Phone cord for connection to phone system

•

Dial out access prefixes, and long distance access code if required. (ie, dial

•

9 for local line)
ISP account or Modem Server phone number (check with ISP)

•

DNS server address. (check with ISP)

•

Time to dial. If phone line is shared, choose a time of day when other

•

devices are not in use
A regular telephone for line testing and diagnostics

•

For dialin installations only (AcquiSuite DR receives/answers a phone call from your
computer):

Phone line with dialtone. Must be NOT shared with other devices. (or use

•

appropriate line sharing device)
Phone cord for connection to phone system

•

Telephone number for the phone line that the AcquiSuite DR will be

•

attached to (so you can call the AcquiSuite DR)
Make note of the AcquiSuite DR dialin IP/Netmask for future use.

•

A regular telephone for line testing and diagnostics

•

hardware overview

Processor

Arm9 embedded CPU

Operating system

Linux

Flash memory

16 MB flash

Memory

32 MB RAM

LED

8x input, 4 modem activity, Modbus TX/RX, ppower,

system, io status

Console

2 x 16 LCD (passive), two pushbuttons

LAN

RJ45 10/100 Ethernet, full half duplex

Modem

V.34 bis, 33,600 bps

Protocols

Modbus/RTU, Modbus/TCP, TCP/IP, PPP, HTTP/HTML, FTP,

NTP, XML

Power requirements

120-240 VAC

Power supply

Included, 24 VDC, Class 2 transformer

Interval recording

User selectable 1-60 minutes; default 15 minute interval

Serial port

RS-485 Modbus, supports up to 32 external devices

(expandable)

Inputs

8x inputs with multiple modes: 0-10V/4-20mA (min/

max/average/instantaneous data); pulse/dry contact

(consumption/rate/runtime/status)

Size

8" x 9.25" x 2.5"