Wiring boarD

2. 24VAC/DC Relay Control

4. N.O. Block

1. Line Current Terminals

3. N.C. Block

1

3

2

4

installation

Prior to installation, disconnect and lock out all power sources.

1. Open the device. Set aside the lid and the bag of hardware enclosed.

VERIS INDUSTRIES, INC.

PO

RTLA

ND,

OREG

ON

USA

TOLL FREE U

SA 1.800.354.8

556

TEL USA

1.503.598.4564

FAX USA

1.503.598.4664

535

HAND

OFF

AUTO

CAUTION: Consu

lt instructions

prior to installation

!

STATU

S OUT

PUT: 1

A@30V

AC/DC

RELAY

COIL:

24VAC

/DC; 1

6mA n

om.

RELAY

OUTP

UT: 16

(8)A@2

50VAC

; 3/4 H

P

RS

OC

SO

SP

SC

2. Wire the 24 AC/DC relay control through the top hole of the device. Use only copper

conductors for command relay inputs. Tighten terminal blocks to 3.5 in-lb (0.4
N-m) torque. Keep wires away from the N. O. and N. C. jumper blocks.

24VAC/DC Relay Control /
Status Control

Status Output & Relay Coil
(Low Voltage Wires Only)

3. Set the relay contact jumper for N.O. or N. C. operation (the device is shipped with

the jumper set in the N.O. position).

N.C. Block

N.O. Block

4. Select one of the following mounting configurations (a, b, c, or d) to match your

installation.

a.) duplex box:

Mounting slot

Mounting hole

Line Voltage

Wires

Connect line voltage wires
to line current terminals

N.O. Block

N.C. Block

Wire the 12 AWG lines from the controller through the back of the device, to
the line current terminals. Tighten line current terminal blocks to 12 in-lb.
(1.35 N-m) torque. Use the base as a template for mounting to the wall using
the mounting hole and slot shown.

b.) 4S junction box:

Line Voltage

Wires

Connect line voltage wires
to line current terminals

Mounting hole

Mounting hole

Wire the 12 AWG lines from the controller through the side of the device, onto
the line current terminals. Tighten line current terminal blocks to 12 in-lb.
(1.35 N-m) torque. Use the base as a template for mounting to the wall using
any of the mounting holes shown.

c.) surface mounting:

Line Voltage
Wires

Connect line voltage wires
to line current terminals

Wire the 12 AWG lines from the controller through the side of the device, onto
the line current terminals. Tighten line current terminal blocks to 12 in-lb.
(1.35 N-m) torque. Use the base as a template for mounting to the wall using
any of the mounting holes shown.