Veris Industries PX SERIES Datasheet User Manual

Dry media differential pressure transducers, Px series, Pressure

Advertising
background image

PRESSURE

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

SPECIFICATIONS

Media Compatibility

Dry air or inert gas

Input Power

12-30VDC, or 24VAC nominal; 2-wire: 20mA max.; 3-wire: 30mA max.

Output

Field-selectable: 2-wire, loop-powered 4-20mA (DC only, clipped and capped), or 3-wire 0-5V/0-10V *

Pressure Ranges:

PX: 01

Unidirectional: 0.1/0.25/0.5/1.0” W.C. F.S., switch selectable

Bidirectional: ±0.1/±0.25/±0.5/±1.0” W.C. F.S., switch selectable

Unidirectional: 25 Pa/50 Pa/100 Pa/250 Pa, F.S., switch selectable

Bidirectional: ±25 Pa/±50 Pa/±100 Pa/±250 Pa, F.S., switch selectable

PX: 02

Unidirectional: 1.0/2.5/5.0/10” W.C. F.S., switch selectable

Bidirectional: ±1.0/±2.5/±5.0/±10” W.C. F.S.,switch selectable

Unidirectional: 0.250 kPa/0.500 kPa/1.000 kPa/2.500 kPa, F.S., switch selectable

Bidirectional: ±0.250 kPa/±0.500kPa/±1.000 kPa/±2.500 kPa, F.S., switch selectable

PXU: 05

Unidirectional: 0.1/0.25/0.5/1.0/2.5/5/10” W.C. 25 Pa/50 Pa/100 Pa/250 Pa/0.5 kPa/1 kPa/2.5 kPa F.S. switch selectable

Bidirectional: ±0.1/0.25/0.5/1.0/2.5/5/10” W.C. 25 Pa/50 Pa/100 Pa/250 Pa/0.5 kPa/1 kPa/2.5 kPa F.S. switch selectable

Response Time

Standard: T95 in 20 sec, Fast: T95 in 2 sec, switch selectable

Mode

Unidirectional or bidirectional, switch selectable

Display (option)

Signed 3-1/2 digit LCD, indicates pressure, overrange indicator

Proof Pressure

3 psid (20.6 kPa)

Burst Pressure

5 psid (34.5 kPa)

Accuracy

±1% F.S. of selected range (combined linearity and hysteresis)

Temperature Effect

1" (250 Pa) models: 0.05%/°C; 10" (2.5 kPa) models: 0.01%/°C; (Relative to 25°C) 0° to 50°C (32° to 122°F)

Zero Drift (1-year)

1" (250 Pa) models: 2.0% max.; 10" (2.5 kPa) models: 0.5% max.

Zero Adjust

Pushbutton auto-zero and digital input (2-pos terminal block)

Operating Environment

0°- 60°C (32° to 140°F); 0 to 90% RH noncondensing

Fittings

Brass barb; 0.24” (6.1 mm) o.d.

Physical

UL 94 V-O Fire Retardant ABS

EMC Conformance: Low voltage directive 2006/95/EC; EMC directive 2004/108/EC.

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).

* Minimum input voltage for 4-20mA operation: 250 Ω loop = 13VDC; 500Ω loop = 19VDC

DESCRIPTION

The digital PX Series differential pressure transducers utilize highly accurate,
microprocessor profiled sensors and an advanced ceramic capacitive sensing
element. Designed to monitor duct and room pressure in commercial buildings, the

PX Series offers exceptional job-site flexibility. PXP and PXD models feature four

field-selectable ranges. The PXU features seven field-selectable ranges, allowing just

one model to cover applications for 0-0.1” to 0-10” W.C. The directional mode jumper

is used to configure the transducer in unidirectional or bidirectional mode for room

and building static pressure applications. All models feature a pushbutton and digital

input terminal to zero the output. The microprocessor is programmed to prevent

accidental zero adjustment during normal operation.

APPLICATIONS

Static pressure in duct or room applications

Variable air volume system control

Filter status monitoring

Clean rooms, hospitals, fume hoods, computer rooms, and other very low

differential pressure applications

FEATURES

Excellent tolerance to overpressure and vibration reduces field failures

High accuracy digital sensor maintains calibration and reduces callbacks

High reliability sensor technology for long-term maintenance-free operation

Selectable ranges and scales reduce setup time & number of models

to stock

Microprocessor-based design allows for digitally profiled sensor increasing

product accuracy and reliability

Circuit protection prevents damage due to incorrect wiring

Monitors positive and negative pressure for application versatility

Flexibility: standard and fast response modes

LCD is ideal for setting up, troubleshooting, and measuring

Ceramic capacitive sensing element...highly stable linear output, reducing
offset errors

Selectable Ranges, LCD Display,

And Automatic Zero For

Easy Operation

Dry Media Differential

Pressure Transducers

Year

Warranty

5

PXP

PXU

PX SERIES

HQ0001827.B 01131