ENVIRONMENTAL SENSORS

INSTALLATION GUIDE

Wall Mounted Environmental CO

2

Sensors

Installer’s Specifications

Input Voltage

20 to 30VDC, 24VAC

Analog Output

CWL: 4-20mA (clipped and capped)/0-5VDC/0-10VDC (selectable)

CWE: 4-20mA (clipped and capped)/0-10VDC (selectable);

Sensor Current Draw

100mA max.

Operating Temperature Range

No humidity option: 0° to 50°C (32° to 122°F)

With

humidity option**: 10° to 35°C (50° to 95°F)

Operating Humidity Range

0-95% (noncondensing)

Housing Material

High impact ABS plastic

CO

2

Transmitter:

Sensor Type

Non-dispersive infrared (NDIR), diffusion sampling

Output Range

CWL: 0-2000 ppm or 0-5000 ppm, user selectable;

CWE: 0-2000 ppm

Accuracy

±30 ppm ±2% of measured value*

Repeatability

±20 ppm ±1% of measured value

Response Time

<60 seconds for 90% step change

RH Transmitter**:
HS Sensor

Digitally profiled thin-film capacitive (32-bit mathematics);

U.S.

Patent 5,844,138

Accuracy

±2% from 10 to 80% RH @ 25°C; Multi-point calibration NIST

Hysteresis

1.5% typical

Linearity

Included in Accuracy spec.

Stability

±1% @ 20°C (68°F) annually for two years

Output Range

0-100% RH

Temperature Coefficient

±0.1% RH/°C above or below 25°C (typical)

Temperature (Transmitter)**:

Sensor Type Thermistor

Accuracy

±0.5°C (±1°F) typical

Resolution

0.1°C (0.2°F)

Output Range

10° to 35°C (50° to 95°F)

Relay Contacts**:
1 Form C (on models without setpoint slider option)

1A@30VDC, resistive; 30W max.

Specified accuracy with 24VDC supplied power with rising humidity. RTD/Thermistors in wall

packages are not compensated for internal heating of product.

EMC Conformance: EN 61000-6-3:2001 Class B, EN 61000-6-1:2001, EN 61000-3-2:2000, EN

61000-3-3:2001

EMC Test Methods: CISPR 22:1997(Amended A9:2000, A2:2002), IEC 61000-4-2:2001, IEC 61000-4-

3:2002, IEC 61000-4-4:2004, IEC 61000-4-5:2001, IEC 61000-4-6:2004, IEC 61000-4-8:2001, IEC

61000-4-11:2004.

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor

with proper SURGE PROTECTION (EN 61000-6-1:2001 specification requirements)

* Measured at NTP

** Not available on CWE

Note: Rough handling and transportation may cause a temporary reduction of CO

2

sensor

accuracy. With time, the ABC function will tune the readings back to the correct accuracy range.

The default tuning speed is limited to 30 ppm per week.

CW SerieS

CW SerieS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

PRODUCT IDENTIFICATION

RH Option Temp Sensor Type

A = Transmitter
B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Therm.
E = 2.2k, Therm.
F = 3k, Therm.
G = 10k CPC, Therm.
H = 10k T3, Therm.

T = Temp
X = No
(stop here)

H = RH 2%
X = No RH

CWL

CWE

WALL DELUXE MODELS:

WALL ECONOMY MODELS:

Sensor Type

B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Therm.
E = 2.2k, Therm.
F = 3k, Therm.
G = 10k CPC, Therm.
H = 10k T3, Therm.
J = 10k Dale, Therm.

S

S

CWL

CWE

Temp Cal Cert Option Setpoint Slider Value

1 = Push Button
Override *
2 = Set Point Slider
3 = Push Button
Override*+Set Point
Slider

A = 1k
F = 10k
G = 20k
K = 50k
M =100k

Options Available

X = No
1 = 1pt Temp Cal
2 = 2pt Temp Cal

* Note: the Pushbutton Override
feature is not available with
temperature transmitter models.
Only resistive temperature models
qualify for this feature.

K = 10k w/11k shunt, Therm.
M = 20k NTC, Therm.
N = 1800 ohm, Therm.
R = 10k US, Therm.
S = 10k 3A221, Therm.
T = 100k, Therm.
U = 20k “D”, Therm.

J = 10k Dale, Therm.
K = 10k w/11k shunt, Therm.
M = 20k NTC, Therm.
N = 1800 ohm, Therm.
R = 10k US, Therm.
S = 10k 3A221, Therm.
T = 100k, Therm.
U = 20k “D”, Therm.

QUICK INSTALL

1. Select a mounting location away from ventilation sources. The sensor should be

mounted on a vertical wall, about 4 1/2 feet above the floor.

2. Affix the backplate to the wall.

3. Wire the device. Refer to wiring diagrams on page 2.

4. Install Cover.