Adjustable Solid-Core Current Switch

with 250 VAC/DC Output

SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Amperage Range

1 to 135A Continuous

Status Output Ratings

N.O. 1.0A@250VAC/DC, not polarity sensitive

Insulation Class

600VAC RMS

Frequency

50/60 Hz

Hysteresis

10% typical

Temperature Range

-15° to 60° C (5° to 140° F)

Humidity Range

10-90% RH non-condensing

Off State Resistance

Open switch represents 1+ MΩ

On State Resistance

Closed switch represents <200 mΩ

Terminal Block Wire Size

24 to 14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

CE EN 61010-1

Installation Category

Cat III, pollution degree 2

The product design provides for basic insulation only.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and

operation of this electrical equipment and the installation, and has received safety

training to recognize and avoid the hazards involved.

NEC2009 Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

DANGER

WIRING EXAMPLE

TM

709HV

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

INSTALLATION

Disconnect and lock out power to the enclosure

containing the conductor to be monitored.

1. Locate a mounting surface for the removable mounting bracket that will allow the

monitored conductor to pass through the center window when it is installed and
that will keep the device at least ½” (13 mm) from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.

2. Drill holes to mount the bracket to the chosen surface using the included screws.

3. Wire the output connections between the sensor and the controller (solid-state

contact).

4. Route the conductor through the sensor’s center window and slip the assembly

into the mounting bracket.

5. Secure the enclosure and reconnect power.

6. Calibrate the sensor (see page 2) with the load running normally.

Fan or Pump

CONTACTOR

DDC CONTROLLER

DI

Motor

0.2” x 0.15”

slot (2x)

1.1"

(27 mm)

2.8"

(68 mm)

0 0.7"

(19 mm)

0.9"

(23 mm)

3.0"

(75 mm)

Removable/Adjustable Mounting Bracket

3.8"

(95 mm)

4.2"

(106 mm)

Two pairs of terminals are used for the switched output. Each pair is one connection, and both
terminals in that pair are internally connected together. The connections are not polarity sensitive.