Veris Industries LD2100 Datasheet User Manual

Distance read panel, Helps eliminate high humidity false alarms, Le ak dete ction

Advertising
background image

LE

AK DETE

CTION

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Helps Eliminate High

Humidity False Alarms

Distance Read Panel

DESCRIPTION

Together with our SC, SC-C, or SC-H sensing cable, the LD1500 and LD2100 panels

detect and report the presence and exact location of the cable-specific fluid. When

the fluid comes in contact with the patented cable, the monitoring panel quickly

pinpoints the location of the leak, triggering an alarm and displaying the location.

FEATURES

●

Adjustable leak and contamination alarm thresholds to prevent false alarms

due to high humidity...high detection accuracy

●

RS-232 port allows configuration with PC

SPECIFICATIONS

Input Power

24VAC@600mA max., 50/60 Hz; 24VDC@600mA max.

Inputs:

Water Leak Detection Cable

Requires 15 ft. (4.5 m) leader cable kit (LC-KIT or LC-KIT-M)

Maximum Length

1500 ft. (457 m); LD2100: 2000 ft. (609 m)

Detection Accuracy

± 2 ft (0.6 m) + 0.5% of the cable length

Detection Repeatability

± 2 ft (0.6 m) + 0.25% of the cable length

Detection Response Time

5-995 sec ± 2 sec

Outputs:

Relay (LD2100 only)

1A@24VDC, 0.5A resistive@120VAC

Communications Ports:

RS-232

9600 baud, No parity, 8 data bits, 1 stop bit

RS-485

1200, 2400, 9600, or 19200 baud (selectable); No parity, 8 data bits, 1 stop bit

Protocols:

Terminal Emulation (RS-232)

VT100 compatible

Modbus (RS-485)

Slave; RTU Mode; Supports function codes 03, 04, 06, and 16; Johnson N2 (LD2100 only)

Expanded Protocols:

TCP/IP, HTML, TFTP IPv4.0

SNMP

V1: V2C MIB-2 compliant; NMS Manageable with Get, Set, Traps

SMTP (email, LD2100 only)

Supports client authentication (plain and login); compatible with ESMTP servers

Modbus TCP/IP

Modbus slave; TCP/IP transmission protocol

BACnet/IP

ASHRAE Std 135-2004 Annex J

Alarm Notification:

Audible Alarm

LD2100: 70 dBA@2 ft. (0.6 m); re-sound configurable (disabled, 0 to 24 hours, integer values only)

Visual Alarm

LD1500: Red, 4-digit; 7 segment LED display; bi-color status LED; LD2100: bi-color status LED

Email (LD1500/LD2100)

4 email recipients; email sent on Alarm and Return to Normal

SNMP Traps (LD1500/LD2100)

4 community strings

Logging Capabilities:

Event Log

LD1500: Last 10 events; LD2100: Last 500 events

Trend Log

LD2100: Cable current level every day, for the last 288 days

Login Security :

Display Access

1 Administrator (password for configuration, no password required to view panel status)

Front Panel Interface:

Display

LD2100: green alphanumeric dot matrix

Push Buttons

LD2100: Test/Rest; LD5200: Up, down, right, left, enter

LED Indicator

LD1500: 1 tri-color Power/Status (green = power on; red = alarm; yellow = cable fault; LD2100: 1 bi-color Power/Status (green=power on, red=alarm)

Operating Environment:

Temperature

0° to 50°C (32° to 122°F)

Humidity

5% to 95% RH non-condensing

Altitude

15000 ft. (4572 m) max.

Mounting

Vertical wall mount (DIN rail mounting option available on LD2100 only)

Agency Approvals

CE; ETL listed: conforms to UL 61010-1, EN 61010-1; CSA C22.2; RoHS compliant,

LD2100

LD1500

LD1500 & LD2100

HQ0001796.B 01131