INSTALLATION GUIDE

Split-Core Current Transducer,

0-10VDC Output

Installer’s Specifications

Amperage Range

0-20/100/150A (slide-switch selectable)

Sensor Power

Induced from monitored current

Insulation Class

300VAC RMS

Frequency Range 50/60Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10 - 90% RH, non-condensing

Accuracy

±2% full scale from 10% to 100% (selected range)

Response Time

2 sec.

Terminal Block Maximum Wire Size

14 AWG

Terminal Block Torque (nominal)

4 in-lbs (0.45 N-m)

Agency Approvals

CE: EN61010-1:2001-2, CAT III, pollution degree 2, basic insulation

For applications requiring double or reinforced insulation, please contact the factory

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

WIRING EXAMPLE

H923

TM

923

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

Fan or Pump

CONTROLLER

0-10VDC

COMMON

+

AI

CONTACTOR

Removable Mounting Bracket

Self-gripping

Iris

1.0”

(25 mm)

0.8”

(21 mm)

1.1”

(26 mm)

3.1”

(79 mm)

2.8”

(70 mm)

Ø = 0.3”

(8 mm)

1.4”

(36 mm)

2.5”

(64 mm)

3.0”

(76 mm)

Bracket can be mounted
on three sides for added
installation flexibility.

Use DIN Rail

Mounting clip

(Veris part

number AH01) to

mount on stan-

dard DIN rail.

INSTALLATION

Disconnect and lock out power to the enclosure containing the

conductor to be monitored.

1. Locate a mounting surface for the removable mounting bracket that will allow

the monitored conductor to pass through the center window when it is installed
and that will keep the device at least 1/2” from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.

2. Drill holes to mount the bracket to the chosen surface using the included screws.

3. Set the desired amperage range (20, 100, or 150 Amps).

4. Wire the output connections between the sensor and the controller (0-10VDC).

5. Snap the sensor over the conductor to be monitored and clip the assembly to the

mounting bracket.

6. Scale the controller software to match the sensor output.

7. Secure enclosure and reconnect power.