Veris Industries EP3 Datasheet User Manual

Electropneumatic transducers, Ep series, Pressure

Advertising
background image

PRESSURE

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Electropneumatic Transducers

Micro-Controlled With High-

Performance, Low-Power Coil

Poppet Valve Technology

EP SERIES

EP3

SPECIFICATIONS

Input Power

22-30VDC/20-30VAC, 47-63 Hz,150mA max. average, 350mA peak

Control Input

4-20mA/0-5V/0-10VDC; switch-selectable, Tri-State, PWM

Input Impedance

4-20mA, 250 Ω; 0-5V/0-10VDC, 10 kΩ

Manual Override

Digital pushbutton adjust, switch-selectable mode

Alarm Contact

100mA@30VAC/DC (Pressure loss, manual mode, jumper selectable)

Accuracy

1% FS; combined linearity, hysteresis, repeatability @20°C (68°F) ambient

Temperature Coefficient

±0.1%/°C

Operating Environment

10-90% RH noncondensing -4°C to 60°C

SCIM

523 in

3

/min @ 45 psi; (8570 cm

3

/min @ 310.3 kPa); 333 in

3

/min @ 20 psi (5457 cm

3

/min @ 137.9 kPa)

Supply Pressure

Min (0.1 psi + user F.S. pressure); Max 45 psig

Control Range

User programmable Zero selectable from 0-25 psi: Full scale 0-25 psi

Pressure Differential

0.1 psig (supply to branch)

Pressure Indication

Electronic, 3-1/2 digit LCD (back-lit)

Minimum Tubing Length

15 feet*

Port Connection

1/8” i.d. poly tubing

Media Connection

Clean, dry air, or inert gas. Do not use with oxygen service

*For shorter tubing runs use AA45 Pneumatic Capacitor

EMC Conformance: Low voltage directive 2006/95/EC; EMC directive 2004/108/EC.

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power

adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).

Year

Warranty

5

DESCRIPTION

The EP3 Series combines a microcontroller with high performance, low power

coil poppet valve technology to create a system with unparalleled accuracy and

proven reliability. The poppet valves used in the EP3 consume no air, eliminating

unnecessary air losses in the system and allowing for efficient, long-term operation.

The EP3 permits versatility, since all models feature manual override and a tri-state

control option. The LCD provides easy visibility and the LED indicators provide visual

status of valve operation in manual or automatic mode. All models come with

SnapTrack housing and optional covers are available.

APPLICATIONS

Hospitals

Schools

Pneumatic dampers/actuators

FEATURES

Field-selectable 4-20mA/0-5V/0-10VDC input for application flexibility

Poppet valve technology for quiet operation

Manual override with set and hold feature...great for commissioning

those leaky systems

Multi-point calibration; 3-15 psi (5 point calibration) and 0-20 psi

(6 point calibration)

Pressure loss alarm provides a contact closure if the EP3 is unable to

achieve the desired output within a fixed length of time

Failsafe vent solenoids bleed branch pressure on power failure for added safety

Optional transparent plastic dust cover (AA43) protects units from dust

and tampering (required for CE)

User programmable zero and full scale outputs

Backlit LCD for local indication of readings...easy to view

Dual-color LED...assists in trouble shooting

Tristate and PWM inputs

EP Series transducers are sold as an open device.

Observe handling precautions for static sensitive

devices to avoid damage to the circuitry which

would not be covered under the factory warranty.

HQ0001829.B 01131