Veris Industries HED SERIES Datasheet User Manual

Standard duct humidity sensors, 2%, 3%, and 5% accuracies, Hed series

Advertising
background image

HU
MIDIT

Y

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

FEATURES

Monitor humidity and temperature with a single device...reduce installation

costs

Semiconductor, temperature transmitter, or popular thermistor/RTD

sensors available

Tool-less gasketed entry lid...no more lost screws

Large cage clamp terminal blocks...easy hoop-up with no wire nuts

Circuitry is embedded in the probe for durability and protection

Standard Duct

Humidity Sensors

DESCRIPTION

HED Standard Series duct mount humidity transmitters offer high performance
in an easy to install housing at an affordable price. The thin-film capacitive sensor
element provides high accuracy and performance, great long-term stability, and
full recovery from saturation. Temperature sensing options are also available.

The duct-mounted HED includes a rugged all plastic housing with a tool-less
gasketed entry lid, large cage clamp terminal blocks, and sturdy ABS material. All
Standard models come with a standard one-year warranty.

APPLICATIONS

HVAC economizer control

Managing energy systems

Facilitating ASHRAE standards for environmental control

2%, 3%, and 5% Accuracies

SPECIFICATIONS

Input Power:

Input Power, Voltage Version

12-24VDC or 24VAC

Input Power, mA Version 12-24VDC

AC Voltage Tolerance ±10%

AC Frequency

50-60 Hz

Max. Inrush Current after 1 msec (mA version) 25mA

Output Power:

mA Output

4-20mA, 2-wire, not polarity sensitive

mA Max. Loop Resistance

500Ω at 24VDC input voltage; 250Ω at 12VDC input voltage

Voltage Output

0-5V or 0-10V (jumper selectable)

Voltage Min. Load Resistance 5kΩ

Voltage Min. Sinking Current 0.2mA

Humidity:

RH Element

Digitally profiled thin-film capacitive, non-removable

Accuracy

±2%, 3%, or 5% (10-90% RH, 20° to 30°C)

Temperature Effect (Outside 20° to 30°C)

≤0.1% RH per °C

Response Time (to 90% change at 20°C)

110 sec

Annual Drift ≤1%

Output Scaling

0-100% RH

Temperature:

Active Output Accuracy ±0.5°C

Active Output Temperature Scaling

Type 1: -40° to 50°C (-40° to 122°F); Type 2: 0° to 50°C (32° to 122°F)

Self-Heating Error (Resistive Temperature Only)

≤±0.5°C at 20° to 30°C (68° to 86°F); ≤±0.75°C outside of 20° to 30°C (68° to 86°F)

Operating Environment:

Operating Temperature

-40° to 50°C (-40° to 122°F)

Operating Humidity

0-100% RH noncondensing (Unit will recover from saturation)

Housing:

Material

ABS plastic with UL V-0 5VA Flame Class

EMC Conformance: EN61000-6-3:2007+A1:2011 Class B; EN61326-1:2006 Class B; EN61000-6-1:2007

Meets UL requirements for plenum rating.

HED

Year

Warranty

1

HED SERIES

Ideal

for Bid

Spec!

HQ0001719.E 01131

Advertising