Veris Industries Badger 3050 SERIES Install User Manual
Page 3

3
ElECTRICal INsTallaTION:
Power supply Wiring
The Badger® Data Industrial® Series 3050 requires
12-24 VDC/VAC to operate. Check specifications page
for DC current draw, and AC Volt-Amp requirements. A
fused circuit is always recommended.
Connect the positive of the power supply to the Series
3050 terminal marked (ACL/DC+), and connect the
negative of the power supply to the Series 3050 terminal
marked (ACC/DC-).
If a Badger Data Industrial plug-in power supply (Model
A1026, A-503) is being used connect the black-white wire
to the terminal marked (ACL/DC+) and the Black wire to
the terminal marked (ACC/DC-).
Figure 3 ( Power Supply Wiring)
(+) (-)
12-24VDC
Power
Supply
( Line) (Com)
12-24VAC
Power Supply
OR
Earth
or
Panel
Ground
Ground wire should be heavy gauge and as short as possible
Earth
3
LV AC/DC(-) 2
LV AC/DC(+) 1
POWER
Figure 3: Power supply Wiring
Figure 1: Panel Mounting Dimensions
Figure 2: Wall Mounting Dimensions