INSTALLATION GUIDE

H8238

Multi-Circuit Meter

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• SECONDARY LEADS/TERMINALS OF CURRENT OUTPUT (e.g. 5A) CTs MUST BE SHORTED,
OR CONNECTED TO THE BURDEN AT ALL TIMES.
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

A qualified person is one who has skills and knowledge related to the construction and

operation of this electrical equipment and the installation, and has received safety

training to recognize and avoid the hazards involved.

NEC2009 Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found

to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.

SPECIFICATIONS

Electrical Services

Eight 3Ø circuits sharing a common line voltage source

Sample Rate

1280 Hz

Operating Temperature Range

0° to 60°C (32° to 140°F) (<95% RH, non-condensing)

Storage Temperature Range

-40°C to 70°C (-40° to 158°F)

Altitude of Operation

3 km

Systems Accuracy

+/- 1% (target, exclusive of user-supplied CTs)*

Variable Update Rate

200 msec for voltages, 1.6 sec for all others

Measured Voltage Inputs:

Number of Channels

Three (phase A, B, C, plus neutral). Average of phases used

for

L-N values if no neutral present

Maximum Voltage

277VAC L-N +10%; 480VAC L-L +10%

Frequency

50/60 Hz

Terminal Block

4-position Euro style pluggable connector (max. wire size 12 gauge);

torque

5.7 in•b (0.64 N•m)

Measured Current Inputs:

Number of Channels

24 (8 meters x 3 phases/meter)

CT Input Type

5 Amp (customer-supplied)

CT Range

Each of 8 meters independently adjustable from 1A:5A to 9999A:5A

Terminal Block

6-position Euro style cage clamp connector (max. wire size 14 gauge);

torque

4.4 in•lb (0.50 N•m)

Operating Power Inputs:

Power Source

Dedicated 120VAC L-N (H8238) or 240VAC L-N (H8238E); fused 40 mA

Power Voltage Tolerance

+10/-25%

Frequency

50/60 Hz

Terminal Block

2-position Euro style pluggable connector (max. wire size 12 gauge)

Network Connections:

Type

Modbus RTU

Connection

DIP switch-selectable 2-wire or 4-wire

Address

DIP switch-selectable base address (1 to 233 in steps of 8)

Baud Rate

DIP switch-selectable 2400, 4800, 9600, 19200**

Parity

DIP switch-selectable NONE, ODD, EVEN

Communication Format

8-data-bits, 1-start-bit, 1-stop-bit

Terminal Block

5-position Euro style pluggable connector (max. wire size 12 gauge);

nominal

torque 4.0 in•lb (0.45 N•m); maximum torque 5.0 in•lb (0.56 N•m)

Installation Category

Cat III, pollution degree 2

* Accuracy specification valid only when amperages are greater than 10% of maximum CT range.

** Baud rates for H8238EL are 1200, 2400, 4800, and 9600.

QUICK INSTALL

Observe precautions for handling static sensitive

devices to avoid damage to the circuitry that

is not covered under the factory warranty.

1. Connect the current inputs.

2. Connect the voltage leads.

3. Configure the communication switches.

4. Select a network address.

5. Connect the RS-485 connection to the communications wiring.

6. Connect the circuit power.

PRODUCT IDENTIFICATION

MODEL

DESCRIPTION

H8238

Multi-Circuit Monitor, 90-130 VAC supply voltage

H8238E

Multi-Circuit Monitor, 240 VAC supply voltage

H8238EL

Multi-Circuit Monitor, 240 VAC supply voltage, low baud rate version