Veris Industries Hx22 SERIES Datasheet User Manual

Current sensors: 0-5vdc analog output, Load trending with 0-5vdc output, Hx22 series

Advertising
background image

current monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

DESCRIPTION

The Hawkeye 722, 822, and 922 provide accurate load trending information with

a proportional 0-5VDC output signal. Slide-switches provide easy field selection of

monitored amperage range without jumpers (available on most models).

APPLICATIONS

Load trending

Motor control

Positive proof of flow

FEATURES

Self-powered analog current sensor simplifies installation

No external power required for sensor...eliminate power supplies

Self-gripping split-core for fast retrofit installation...no need to remove

conductor (H922)

Economical solid-core models feature adjustable bracket for easy alignment

No jumpers on unit...reduces installation error

Selectable factory calibrated ranges for increased flexibility and resolution

Some models available with three field-selectable ranges per unit...fewer

versions to choose from, stock, and install

Mini-sized H822 fits easily in tight enclosures

Removable bracket on H922 can be installed in three different configurations...

added flexibility

100% solid state, no moving parts to fail

5-year warranty

Load Trending With

0-5VDC Output

EXAMPLE LINEAR OUTPUT

Scale software as shown

SENSED AMPS

Selected Range*

0 VDC

0A

5 VDC

SENSOR OUTPUT

*Factory calibrated ranges selected

with the amperage range switch

SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Insulation Class

600VAC RMS (UL), 300VAC RMS (CE)

Frequency

50/60 Hz nominal

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Accuracy

±2% F.S. from 10% to 100% (selected range)

Response Time

2 sec.

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL 508 open device listing; CE: EN61010-1:2001-2, CAT III, pollution degree 2, basic insulation

For applications requiring double or reinforced insulation, please contact the factory

Current Sensors:

0-5VDC Analog Output

Year

Warranty

5

Maximize Reliability

Minimize Installed Cost

H922

H822

H722LC

Hx22 SERIES

TM

HQ0001764.B 01131

Advertising