Veris Industries H909HV Install User Manual

H909hv, 909hv, Notice

Advertising
background image

TM

CURRENT MONITORING

INSTALLATION GUIDE

Z205454-0E

PAGE 1

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Split-Core Current Switch, Adjustable Trip Point

with 250VAC/DC Output

Installer’s Specifications

Amperage Range

2.5 to 135A Continuous

Sensor Power

Induced from monitored conductor

Max. Current 200A

Frequency

50/60Hz

Switch Output

Max. current: 1A; max. voltage: 250VAC/DC

Hysteresis

10% of setpoint, typical

Insulation Class

300V (CE); 600VAC RMS

Temperature Range

-15° to 60° C (-5° to 140° F)

Humidity Range

10-90% RH non-condensing

Output Resistance - Off-State

0 (open switch represents 1+ MΩ of resistance)

Terminal Block Maximum Wire Size

14 AWG

Terminal Block Torque (nominal)

4 in-lbs (0.45 N-m)

For CE compliance, conductor shall be insulated according to IEC 61010‑1:2001, Installation

Category III or equivalent.

The product design provides for basic insulation only.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

WIRING EXAMPLE

H909HV

TM

909HV

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

INSTALLATION

Disconnect and lock out power to the conductor to be monitored.

1. Locate a mounting surface for the removable mounting bracket that will allow

the monitored conductor to pass through the center window when it is installed
and that will keep the device at least 1/2” from any uninsulated conductors.
Determine cable routing for the output connection, allowing wiring to reach the
mounting location.

2. Drill holes to mount the bracket to the chosen surface using the included screws.

3. Wire the output connections between the sensor and the controller (solid-state

contact).

4. Snap the sensor over the wire to be monitored and clip the assembly to the

mounting bracket.

5. Calibrate the sensor (see page 2) with the load running normally.

Removable Mounting Bracket

Self-gripping

Iris

1.0”

(25 mm)

0.8”

(21 mm)

1.1”

(26 mm)

3.1”

(79 mm)

2.8”

(70 mm)

Ø = 0.3”

(8 mm)

1.4”

(36 mm)

2.5”

(64 mm)

3.0”

(76 mm)

Bracket can be mounted
on three sides for added
installation flexibility.

Use DIN Rail

Mounting clip

(Veris part

number AH01) to

mount on stan‑

dard DIN rail.

Fan or Pump

CONTACTOR

MOTOR

Insulated Conductor

DDC CONTROLLER

DI