SD – Spot Detector

1. Installation

Determine a location. Ram set 6/32 threaded studs in floor on 2.5 inch (63.5mm) centers. Place SD over studs and

secure. Adjust the sense probes to desired height. Connect the white/red and black leads to the FMS, F-Series or

LDRA6 panel. A 24VAC power supply is required for use with a Falcon RA1x2. Test the SD by placing water

under the sense probes.

SD Diagram 1

SD Diagram 2: Falcon Wiring

SD-Z – Zone Spot Detector

1. Installation

Determine a location. Ram set 6/32 threaded studs in floor on 2.5 inch (63.5mm) centers. Place SD-Z over studs

and secure. Adjust the sense probes to desired height. Connect the SD-Z to the LDZ control panel by connecting

the two cable connectors to SeaHawk Water Leak Detection Cable (SC), or SeaHawk Non-Sensing Cable (NSC), or

an end terminator (EOL) as shown in SD-Z Diagram 2. Test the SD-Z by placing water under the sense probes.

SD-Z simulates 50 feet (15.24m) of SC cable: 25 feet in and 25 feet out (7.62m in/out) from device.

SD-Z Diagram 1: Pins

P 1

V D C

T B 1

V D C

+ -

E X T E R N A L

2 4 V D C

+ +

C h 1

+ -

C h 2

+ -

C h 3

+ -

C h 4

+ -

T B 2 In p u t 1 -4

C h 5

+ -

C h 6

+ -

C h 7

+ -

T B 3 In p u t 5 -8

C h 8

+ -

E X T E R N A L

G N D

- -

T B 4

N C N O C

R E L A Y 1

N C N O C

R E L A Y 2

Wh

ite

/Re

d

Bl

ac

k

White/Red (+)

Black (-)

NC Reset

Push Button

24 VDC

(

Polarity is

Not important

)

Once triggered, latches on, until

power is removed (VDC)