Veris Industries Hx00 SERIES Datasheet User Manual

Current switches: fixed trip point, Hx00 series, Current monit oring

Advertising
background image

current monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

FEATURES

●

More reliable for status than relays across auxiliary contacts

●

Ideal for direct-drive units, unit vents, fan coil units, exhaust fans, and other

fixed loads

●

Great for lighting status–less expensive than 277V relays

●

Low 0.15 A turn-on (H300 and H600)...ideal for small exhaust fans (not intended

to detect belt loss)

●

Removable mounting bracket provides installation flexibility

●

Bracket on H900 can be installed in three different configurations...installer

convenience

●

Split-core H300, H600, and H900 for fast retrofit installation

●

Mini solid-core H800 and micro split-core H300 fit in tight enclosures...

saves valuable panel space

●

100% solid-state, no moving parts to fail

●

Polarity insensitive output

●

5-year warranty

Split-Core & Solid-Core On/Off

Status Current Switches

H300

H600

H800

H900

DESCRIPTION

Hawkeye x00 on/off current switches provide a cost-effective solution for

monitoring status on unit vents, exhaust fans, recirculation pumps, and other fixed

loads where belt loss is not a concern.

Veris has applied new technology to the H300, H600, and H800 models to achieve

impressive improvement in turn-on levels. The Hawkeye H300 and H600 now have

the lowest turn-on current in the industry at a mere 150mA!

APPLICATIONS

●

Monitoring status of electrical loads

●

Monitoring direct-drive units, exhaust fans, process motors, and other fixed

loads

●

Verifying lighting run times

Maximize Reliability

Minimize Installed Cost

SPECIFICATIONS

Sensor Power

N.O models: Induced from monitored current; H800NC: 5-30VDC, permanently connected

Insulation Class

600VAC RMS (UL), 300VAC RMS (CE)

Frequency Range

50/60 Hz

Temperature Range

H800, H800NC, H300, H900: -15° to 60°C (5° to 140°F)

H600: -15° to 40°C (5° to 104°F) (to 200A); -15° to 60°C (5° to 140°F) (to 150A)

H800HV: -40° to 50°C (-40° to 122°F) (to 200A); -40° to 75°C (-40° to 167°F) (to 100A, & 0.25A status output)

Humidity Range

10-90% RH non-condensing

Off State Leakage (H800NC Only)

34μA@5VDC, 200μA@30VDC

On State Voltage Drop (H800NC Only)

1.9VDC (max.) @0.1A

Terminal Block Wire Size

H600, H800, H900: 24-14 AWG (0.2 to 2.1 mm

2

); H300: 22-16 AWG (0.3 to 1.3 mm

2

)

Terminal Block Torque

H600, H800, H900: 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m); H300: 7 in-lbs (0.8 N-m)

Agency Approvals

UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation

Do not use the LED status indicators as evidence of applied voltage.

Current Switches:

Fixed Trip Point

US Patent No. 7,193,428

0.15 A

TURN-ON!

(select

models)

Year

Warranty

5

Hx00 SERIES

TM

HQ0001753.B 01131