Solid-Core Current Transducer,

0-5VDC Output

Installer’s Specifications

Amperage Range

0-10/20/40 Amps (slide switch selectable)

Sensor Power

Induced from monitored conductor

Insulation Class

600VAC RMS (UL), 300VAC RMS (CE)

Frequency

50/60Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH, non-condensing

Accuracy

±2% FS from 10% - 100% of selected range

Response Time

2 sec.

Terminal Block Maximum Wire Size

14 AWG

Terminal Block Torque (nominal)

4 in-lbs (0.45 N-m)

Agency Approvals

UL 508 open device listing

CE: EN61010-1:2001-2, CAT III, deg. 2, basic insulation

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

Wiring ExamplE

H722LC

722LC

DimEnsions

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

quick install

Disconnect and lock out power.

1.

Install the mounting bracket to the back of the electrical enclosure, no closer than

2.

1/2” (12mm) to an uninsulated conductor.

Slide the conductor to be monitored through the sensing hole of the current

3.

switch. Terminate the conductor. See Notes (page 2) for currents under 1 Amp or
above 40 Amp.

Set the desired amperage range on the H722LC (10, 20, or 40 Amps).

4.

Wire the output connections between the H722LC and the controller (0-5VDC).

5.

Reconnect power.

6.

Scale the controller software to match the H722LC’s output.

7.

0.2” x 0.15”

slot (2x)

1.1"

(27 mm)

2.8"

(68 mm)

0.7" Dia

(19 mm)

0.9"

(23 mm)

3.0"

(75 mm)

Removable/Adjustable Mounting Bracket

3.8"

(95 mm)

4.2"

(106 mm)

Fan or Pump

CONTROLLER

0-5VDC

COMM

+

AI

VERIS INDUSTRI

ES

Portland, Ore

gon 97223

1-800-354-85

56

CONTACTOR

Insulated Conductor Only