Panelboard Monitoring System

Monitor Current, Voltage,

and Energy Consumption

with One Device

E3x SERIES

power

at

branch

level

E3x Main Board

FEATURES

Revenue Grade measurements

IEC Class 1 metering accuracy

Up to 126 panelboards can be monitored on one RS-485 drop...simplifies wiring

Reports volts, amps, power, and energy for each circuit...one product covers the

whole panelboard

92 circuits with one product (84 branch circuits, 2 3-phase mains, 2 neutrals)...

saves space

3/4”, or 1”, or 18 mm spaced solid-core current sensors...flexible installation

Split-core version has two mounting options (DIN Rail or Snaptrack)...

installation flexibility

4 user-configurable alarm threshold registers...improved load management

Built-in ability to set the orientation and numbering of the circuits

1/4 amp to 100 amp solid-core monitoring...widest dynamic range

in the industry

1, 2, 3 pole breaker support

Applications for new construction (solid-core version) and retrofits

(split-core version)

Modbus RTU standard

Modbus TCP over Ethernet available with addition of U013-0012...page 166

BACnet IP or MS/TP available with addition of E8950...see page 164 (E30Ax84

and E31Axxx not supported)

DESCRIPTION

The E3x Series Panelboard Monitoring System provides a cost effective solution for
electrical load management, making it ideally suited for applications where loads
are dynamic, such as the data storage industry, lighting panels, etc.

The E3x series monitors the current, voltage, and energy consumption of each
circuit in a panelboard including the main breaker. The accumulated information
can be transmitted through the communications interface. Data updates
occur roughly every two seconds to provide timely preventative maintenance
information. As a circuit approaches the user-configured thresholds, alarm
indicators are triggered, preventing costly downtime from overloaded circuits or
failed loads. (See graph, facing page)

APPLICATIONS

Load based cost allocation

Overload protection

Load management

Load balancing

Lighting circuits

SPECIFICATIONS

Inputs:

Input Power

90-277VAC, 50/60 Hz

Accuracy:

Power/Energy

IEC 62053-21 Class 1, ANSI C12.1-2008

Voltage

±0.5% of reading 90-277V line-to-neutral

Operation:

Sampling Frequency

2560 Hz

Update Rate

1.8 seconds (both panels)

Outputs:

Type

Modbus RTU

Connection

DIP switch-selectable 2-wire or 4-wire, RS-485

Address

DIP switch-selectable address 1 to 247 (in pairs of 2)

Baud Rate

DIP switch-selectable 9600, 19200, 38400

Parity

DIP switch-selectable NONE, ODD, EVEN

Communication Format

8-data-bits, 1-start-bit, 1-stop-bit

Termination

5-position depluggable connector (TX+ TX- SHIELD TX+/RX+ TX-/RX-)

Terminal Block Torque

4.4 to 5.3 in-lb (0.5 to 0.6 N-m)

Mechanical:

Ribbon Cable Support

4 ft. (0.9 m) ribbon cable ships standard; up to 20 ft. (6 m) flat and round cables available

Environmental:

Operating Temperature Range

0° to 60°C (32° to 140°F) (<95% RH noncondensing)

Storage Temperature Range

-40° to 70°C (-40° to 158°F)

Altitude of Operation

3000 m

Agency Approvals

UL508, EN61010

Year

Warranty

5

NEW

BACnet

connec

tivity

via new

E8950

Gateway