Veris Industries H535 Install User Manual

Notice, Danger, Enclosed relay

Advertising
background image

TM

CURRENT MONITORING

INSTALLATION GUIDE

Z202808-0E

PAGE 1

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

07121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Enclosed Relay

Installer’s Specifications

Sensor Power

Induced from the monitored conductor

Amperage Range

0.25 to 15 A

Frequency Range

50-60 Hz

Operating Temperature Range

-15° to 50°C (5° to 122°F)

Operating Humidity Range

0-95%, noncondensing

Wire to Relay Contacts

Use 12 AWG (3.3 mm2) wire or larger*

Relay Switching Capacity at 120 VAC

1 HP

Relay Output

SPST F.S. N.O. or N.C., 15 Amps

Relay Coil

24 VAC/DC; 36 mA nom.

Terminal Block Torque

Relay control terminals: 3.5 in-lb (0.4 N-m)

All

other terminals: 12 in-lb (1.35 N-m)

Agency Approvals

UL508, Installation Category III

* For current loads up to 10A, use 75°C rated wire insulation. For loads greater than 10A, use 90°C

rated wire insulation.

The product design provides for basic insulation only.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

H535

535

Dimensions

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

2.13"

(55 mm)

1.16"

(30 mm)

4.25"

(108 mm)

1.53"

(39 mm)

C L

C L

C L

Wire

Opening

Wire

Opening

Wire

Opening

1.16"

(30 mm)

4.25"

(108 mm)

Quick install

1. Disconnect power sources prior to installation.

2. Remove the sensor lid and wire the command relay connections and relay controls

to the base.

3. Set the relay contact jumper.

4. This device has four wiring options, detailed on page 2-3 of this installation guide.

Choose the option appropriate to the application and follow instructions.

operation

The H535 combines a switching relay and a Hand-Off-Auto (HOA) switch in a single
housing. The H535 is connected in series between the power source and the motor
device. It operates at amperages up to a maximum of 15 A, and the relay and HOA
switch control the on/off functioning of the motor. The H535 requires no additional
power source for operation.

TM

Advertising