Direct Current String Monitor

DC Monitoring for Combiner Boxes

DESCRIPTION

The EA10 DC monitoring system provides the perfect solution for string monitoring
in combiner and sub-combiner boxes or other DC loads. The modular construction
allows easy installation for monitoring 8 to 32 strings in a single system. Pulse Reset
technology means no output drift and immunity to power spikes and surges up to
20kA.

This system includes a communications unit that supplies power and provides
Modbus communication. Up to four current sensing modules can connect serially
to one communications unit, each with eight DC current sensors, for a total of 32
monitoring nodes. Connect up to 63 communications units in a daisy chain for
full system monitoring. All boards can be mounted on standard DIN rail for easy
installation.

APPLICATIONS

●

Renewable energy and string monitors

●

Industrial monitoring

●

Data centers

FEATURES

●

Pulse Reset technology...high immunity to power surges...greater repeatability

over time

●

Modular construction...connect up to four current sensing modules to one

communications unit...easy to install

●

Fully encapsulated...robust design is resistant to the elements

●

Monitors 2016 points total...minimize home run wiring

●

Up to 1000VDC isolation for high voltage strings

●

RS-485 Modbus communications...quick commissioning

●

Wide range DC power requirements...versatility

●

Fits onto standard 35 mm DIN rail...convenient installation

●

Amp-hour calculation...read once per day for less network traffic

●

LED indication of faults...quick visible troubleshooting

●

May be installed in UL1741 systems...smart combiner capability

Maximize Reliability

Minimize Installed Cost

SPECIFICATIONS

Inputs:

Control Power

Class 2/SELV 24VDC to 42VDC

Maximum Power Consumption

7W at 32 channels

Maximum Current Input

Up to 20A per point

Accuracy:

Current

0.5% full scale (combined linearity, hysteresis, and repeatability)

Outputs:

Communication

2-wire RS-485, 1200 to 38400 baud, Modbus RTU

Available Information

Current per point, both instantaneous amps & cumulative amp-hours, events

Update Rate

2 sec

Maximum Measurement Points

8, 16, 24, or 32

Mechanical:

Mounting

T35 (35 mm) DIN Rail per EN50022

Terminal Block Wire Size

24 to 12 AWG (0.21 to 3.31 mm

2

)

Terminal Block Torque

0.37 ft-lb (0.5 N•m) nominal/0.44 ft-lb (0.6 N•m) max.

Insulation (from current sensor to control power or RS-485 interface)

Up to 1000 VDC (insulated conductor)

Dielectric Strength

10000 VDC

Environmental:

Operating Temperature Range

-30° to 75°C (-22° to 167°F)

Storage Temperature Range

-40° to 85°C (-40° to 185°F)

Humidity Range

<95% RH noncondensing

Altitude of Operation

3 km

Agency Approvals:

US and Canada Recognized (cRUus)

UL61010-1, Acceptable in UL1741 Combiner Box

Europe (CE)

EN61010-1

Installation Category

Cat. IV, pollution degree 3

EMC:

Conducted and Radiated Emissions

FCC Part 15 Class B, EN55011 / EN61000 Class B (residential and light industrial)

Conducted and Radiated Immunity

EN61000 Class A (heavy industrial)

EA10