Veris Industries Hx06 SERIES Datasheet User Manual

Hx06 series, Current monit oring

Advertising
background image

current monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Current Switches: Adjustable

Trip Point, N.C. Output

Year

Warranty

5

DESCRIPTION

Hawkeye x06 Series solid- and split-core current switches provide accurate, reliable,

and maintenance-free fan and pump status indication.

APPLICATIONS

Monitoring fans, pumps, motors, and other electrical loads for proper operation

Detecting belt loss and motor failure...ideal for fan and pump status

Verifying lighting circuit loads

Monitoring critical motors (compressor, fuel, etc.)

Monitoring industrial process equipment status (OEM)

FEATURES

Adjustable trip point...4 amperage range options for versatility

Easier to install than differential pressure switches...no tubing needed

100% solid-state, no moving parts to fail

Output status LEDs for fast setup

Adjustable mounting bracket on the solid-core housing...easy placement

Self-gripping iris on the split-core housing for easy installation

Bracket on H906 can be installed in three different configurations...added

flexibility

5-year warranty

Detect Belt Loss, Coupling

Shear, And Mechanical Failure

SPECIFICATIONS

Sensor Power 5-30VDC

Insulation Class

600VAC RMS (UL), 300VAC RMS (CE)

Frequency Range

50/60 Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Hysteresis

10% Typical

Off State Leakage

34μA@5VDC, 200µA@30VDC

On State Voltage Drop

1.9VDC [email protected]

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation

Do not use the LED status indicators as evidence of applied voltage

Maximize Reliability

Minimize Installed Cost

H906

H606

H806

H706

Hx06 SERIES

TM

DETECTS BELT LOSS/COUPLING SHEAR!

DETECTS BELT LOSS/COUPLING SHEAR!

Now you can easily detect when drive belts slip, break, or pump couplings shear.

In fact, a typical HVAC motor that loses its load has a reduction of current draw

of up to 50%. That’s why our sensors are the industry standard for status.

Calibrated

Trip Point

Off

Off

Fan/pump

On

Loss of Belt/Coupling Shear

Electrical

Failure

HQ0001756.B 01131

Advertising