Veris Industries TWS SerieS Datasheet User Manual

Independent heat/cool or analog setpoint outputs, Tws series, Setp oint de vices

Advertising
background image

setp

oint de

vices

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Independent Heat/Cool Or

Analog Setpoint Outputs

Wall Mount Temperature

Transmitter with

Thermostat Functions

FEATURES

●

Independent heat/cool (TWS relay) or analog setpoint outputs (TWS analog)

provide application flexibility

●

LCD for local display of readings and setup values...easy visibility under any

lighting conditions

●

Offset function adjusts calibration offsets for temperature

●

Switch selectable 4-20mA or 0-5/0-10VDC analog outputs

●

Semiconductor temperature sensor can be field calibrated

DESCRIPTION

All TWS Series institutional grade temperature transmitters are field-programmable

and are designed to satisfy the demanding requirements of pharmaceutical labs,

hospitals, science labs, and other exacting applications. Internal jumpers control

access to a feature which allows field adjustment of calibration offsets. Tampering

can be prevented by setting a jumper to disable keypad program functions.

Analog Output

Analog output models feature a keypad to make adjusting temperature setpoint

values easy. They are unique in reporting the setpoint values back to a control system

by means of 4-20mA or 0-5/0-10VDC (output selected by slide-switch) signals.

Setpoint Relay

The TWS Series setpoint relay models measure temperature and offer thermostat

functionality. Two separate relays can be configured to control heat/cool in

thermostat mode.

APPLICATIONS

●

Hospitals and operating rooms, pharmaceutical labs

●

Clean rooms

●

Food processing plants

●

Environmental testing facilities, and other institutional applications

SPECIFICATIONS

Input Power

15-30VDC/24VAC, 100mA max.

Outputs, Analog

Switch-selectable 4-20mA (clipped and capped)/0-10V/0-5VDC (switch affects all outputs)

Outputs, Relay (Relay models only)

2 Form C (SPDT), 1A 30VDC, resistive, 30W max.

Temperature:

Accuracy

±0.5°C (±1°F)

Scaling

10° to 35°C (50° to 95°F) or 0° to 50°C (32° to 122°F), menu selectable

Calibration Offset

Adjustable ±10° in 0.1° (C or F) increments

Setpoint Range

Minimum to Full Scale in 1° (C or F) increments

Hysteresis (Deadband)

1° to 10°F in 1°F increments

Physical

UL 94-V-O fire retardant ABS

Year

Warranty

5

TWS

TWS SERIES

HQ0001873.B 01131