DESCRIPTION

The Hawkeye TruStat H10F is a microprocessor based, self-learning, self-calibrating

current switch. It provides calibration-free status, for both under-current and over-

current conditions. At initial power-up, the H10F automatically learns the average

current on the line with no action required by the installer. Once a current is learned,

the switch monitors for changes in current greater than ±20% of the learned load.

APPLICATIONS

●

Verifying lighting circuit and other electrical service run times

●

Monitoring status of industrial process equipment

●

Monitoring status of critical motors (compressor, fuel, etc.)

FEATURES

●

Automatic adjustable trip point (3.5-100A)...precise control of current trip point

●

100% solid state...no moving parts to fail

●

Removable mounting bracket for installation flexibility

●

5-year warranty

●

Automatic calibration...reduced errors and installation costs

●

Microcontroller based learning technology...automatically learns load upon

initial power-up...eliminates labor associated with calibration

●

Monitors current for both under- and over-load in one package

●

Small size fits easily inside small starter enclosures...saves space

Automatically Learns At

Initial Power-Up

Current Switch: Auto

Calibration, Process Control

ALARM RESET
5% Typical

+20%
+15%

POWER

ON

POWER LOSS

ØAAC

ØAAC

-15%
-20%

LEARN
(MODE)
30 SEC

ALARM
(MODE)

ALARM
(MODE)

NORMAL
(CURRENT
MONITOR
MODE)

NORMAL
(CURRENT
MONITOR MODE)

NOMINAL
LEARNED
CURRENT

1 SEC. DELAY 30 SEC. DELAY

Maximize Reliability

Minimize Installed Cost

Year

Warranty

5

H10F

Hawkeye

®

TruStat™

SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Isolation

600VAC RMS (UL); 300VAC RMS (CE)

Temperature Range

-15° to 60° C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Frequency Range

50/60 Hz

Trip Point Calibration Learn Period

30 sec. learn period

Normal-to-Alarm Status Output Delay

1 second max.

Alarm-to-Normal Status Output Delay

30 seconds nominal*

Status Output

±20% of learned current to trigger alarm; ±15% of learned current to release alarm (see graph)

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation

*If current switch experiences a momentary loss of power, 30 second delay may or may not apply.

Do not use the LED status indicators as evidence of applied voltage.

PRODUCT FUNCTIONS

H10F

HQ0001757.B 01131