Veris Industries C SERIES Datasheet User Manual

Deluxe duct and wall co2 sensors, Individual or 3-in-1 co2, rh, and temperature, C series

Advertising
background image

AIR QU

ALIT

Y

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

DESCRIPTION

CDL/CWL carbon dioxide sensors maximize energy savings, while ensuring optimal

ventilation. These sensors allow ventilation systems to be controlled by the amount

of CO2 present in a space. The CWL/CDL Series detect fluctuations in CO2 levels and

signal ventilation systems to provide an inlet of fresh air optimal for the space at a

given time saving energy and ensuring tenant comfort.

APPLICATIONS

●

Controlling ventilation in response to occupancy

●

Facilitating compliance with ASHRAE 62.1 standard for air quality

●

Office buildings, conference rooms, schools, retail stores, etc.

Individual or 3-in-1 CO2,

RH, and Temperature

Deluxe Duct and Wall

CO2 Sensors

SPECIFICATIONS

Input Power

20 to 30VDC/24VAC; 100mA max.

Analog Output

4-20mA (clipped & capped)/0-5VDC/0-10VDC (selectable)

Operating Temperature Range

CDL: 0° to 50°C (32° to 122°F)

CWL: No humidity option: 0° to 50°C (32° to 122°F); With humidity option: 10° to 35°C (50° to 95°F)

Operating Humidity Range

0 to 95% RH noncondensing

Housing Material

High impact ABS plastic

CO2 Transmitter:

Sensor Type

Non-dispersive infrared (NDIR), diffusion sampling

Output Range

0-2000/5000 ppm (programmable)

Accuracy

±30 ppm ±2% of measured value*

Repeatability

±20 ppm ±1% of measured value

Response Time

<60 seconds for 90% step change

RH Transmitter:

HS Sensor

Fully replaceable, digitally profiled thin-film capacitive (32-bit mathematics) U.S. Patent 5,844,138

Accuracy

±2% from 10 to 80% RH @ 25°C; NIST traceable multi-point calibration

Hysteresis

1.5% typical

Stability

±1% @ 20°C (68°F) annually for two years

Output Range

0-100% RH

Temperature Coefficient

±0.1% RH/°C above or below 25°C (typical)

Temperature Transmitter:

Sensor Type

Solid-state, integrated circuit

Accuracy

±0.5°C (±1°F) typical

Resolution

0.1°C (0.2°F)

Output Range

10° to 35°C (50° to 95°F)

Relay Contacts:

1 Form C (SPDT) (on models without setpoint slider option)

1A@30VDC, resistive; 30W max.

RTD/Thermistors in wall packages are not compensated for internal heating of product.

EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC.

EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).

Note: Rough handling and transportation may cause a temporary reduction of CO

2

sensor accuracy. With time, the ABC function will tune the readings back to the correct accuracy range. The default tuning speed is limited to

30 ppm per week.

FEATURES

●

Microprocessor-based design increases accuracy and reduces installation time

●

Non-dispersive infrared technology (NDIR) repeatable to ±20 ppm ±1% of

measured value...high accuracy measurement

●

Innovative self-calibration algorithm...easy to maintain

●

5-year calibration interval (recommended)

●

Field-selectable outputs for operation flexibility

●

Integrated transducer and probe...eliminates the need to install a separate

pick-up tube

●

Snap-on faceplate...no screws required, making installation and service easy

●

Adjustable duct probe...simplifies installation and airflow monitoring

●

CO2, humidity, and temperature sensing all in one compact device...fewer units

to buy and install

C SERIES

CDL

CWL

HQ0001739.B 01131

Advertising