Veris Industries MSC SERIES Datasheet User Manual

Ceiling mount occupancy sensors, Msc series, Lighting c ontr ols

Advertising
background image

LIGHTING C

ONTR

OLS

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Ceiling Mount

Occupancy Sensors

DESCRIPTION

MSC Series Occupancy Sensors employ passive infrared (PIR) and/or ultrasonic

technologies to accurately detect occupancy and automatically switch room lighting.

The low-profile sensor is ceiling-mounted to maximize motion sensitivity in large

areas with obstructions. With a 360 degree field of view, and up to 2000 square

feet of coverage area, the ceiling-mounted occupancy sensor is ideal for conference

rooms, classrooms, multi-stall bathrooms, and large office areas.

The MSC series also incorporates an integral photosensor to prevent lights from

switching on when sufficient ambient light is present, as commonly found in

windowed areas.

Installation and configuration are simple. The sensor readily mounts to drop ceilings,

and it features front adjustments for setting sensitivity and time delay. The sensor

also features an auxiliary relay for use with building automation and HVAC systems.

APPLICATIONS

Lighting control based on occupancy

Reducing energy usage

Key component for LEED* certification programs

MSC1000 – best for conference rooms, classrooms, and other

general applications

MSCD2000 – best for multi-stall bathrooms, large conference rooms,

and warehouses

MSCU2000 – best for lobbies, aisles, and great for multi-stall bathrooms

FEATURES

Up to 2000 square foot coverage area

360 degree field of view

Daylight level sensing (from 0.5 to 250 foot-candles)...eliminates

unneccessary lighting

Adjustable time delay (preset time delays from 15 seconds [test] to 30

minutes)...provides ultimate flexibility

Adjustable coverage sensitivity (from 60-100%)

Auxiliary relay...easily communicates with building control system

Adjustment compartment cover

LED motion indicator...provides quick visual status

Manual bypass...for easy commissioning

Uses The Latest Passive Infrared

And Ultrasonic Technologies

SPECIFICATIONS

Standards

UL and cUL Listed; FCC part 15 (Class B) for Home and Office Use

Input Voltage

24VDC

Current Consumption@24VDC*:

PIR

21mA nominal

Ultrasonic

34mA nominal

Dual

37mA nominal

Isolated Relay

Contact rating: 1A@24VDC Resistive

Temperature

0° to 50°C (32° to 122°F)

Humidity

Max. 90% RH noncondensing

Dimensions:

MSCU

4.6” (117 mm) diameter, 1.4” (35.1 mm) high

MSCD/MSCP

4.6” (117 mm) diameter, 1.8” (45.7 mm) high

For local line switching control, power must be provided by AA47 Power Pack or an approved equivalent.

*Leadership in Energy and Environmental Design (LEED) is a registered mark of the US Green Building Council

Year

Warranty

1

Coverage Patterns for 9 ft (2.8m) Ceiling Height

PIR Sensor

Ultrasonic Sensor

MSCU

MSCD

Minor Motion

Major Motion

25 ft

(7.7m)

32 ft

(9.8m)

48 ft

(14.7m)

30 ft

(9.2m)

24 ft

(7.4m)

42 ft

(12.8m)

MSC SERIES

HQ0001801.B 01131

Advertising