Solid-Core, Normally Closed Current Switch,

Fixed Trip Point

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and

operation of this electrical equipment and the installation, and has received safety

training to recognize and avoid the hazards involved.

NEC2009 Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

DANGER

WIRING EXAMPLE

TM

800NC

DIMENSIONS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

0 0.7"

(18 mm)

0.4” x 0.2”

Slot (x2)

2.8"

(71 mm)

1.7

(43 mm)

2.3"

(58 mm)

1.1"

(27 mm)

0.9"

(23 mm)

Removable/Adjustable Mounting Bracket

POWER

SOURCE

POWER

SOURCE

BUILDING AUTOMATION

CONTROLLER

UNIT VENT HEATER

DI

DI

SPECIFICATIONS

Sensor Power

5-30VDC, permanently connected

Amperage Range

0.5 - 200A Continuous

Status Output Ratings

N.C. 0.1A@30VDC not polarity sensitive

Insulation Class

600VAC RMS (UL), 300VAC RMS (CE)

Setpoint

Fixed at 0.5 A max. (60 Hz)

Frequency

50/60 Hz

Temperature Range -15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Off State Resistance

34µA@5VDC, 200µA@30VDC

On State Resistance

1.9VDC (max.)@0.1A

Terminal Block Wire Size

14 to 24 AWG (2.1 to 0.2 mm

2

)

Terminal Block Torque

3.5 to 4.5 in-lb (0.4 to 0.5 N-m)

Agency Approvals

UL508, CE: EN61010-1

Installation Category

Cat. III, pollution degree 2

For CE compliance, conductor shall be insulated according to IEC 61010‑1.

Listed for use with 75°C insulated conductors.

INSTALLATION

Disconnect and lock out power to the enclosure

containing the conductor to be monitored.

1. Locate a mounting surface for the removable mounting bracket that will allow the

monitored conductor to pass through the center window when it is installed and
that will keep the device at least ½” (13 mm) from any uninsulated conductors.
Determine cable routing for the output connection, allowing wiring to reach the
mounting location.

2. Drill holes to mount the bracket to the chosen surface using the included screws.

3. Wire the output connections and relay between the sensor and the controller

(solid-state contact).

4. Wire the sensor to external power supply.

5. Route the conductor through the sensor’s center window and clip the assembly to

the mounting bracket.

6. Secure the enclosure and reconnect power.