Veris Industries H723LC Install User Manual

Solid-core current transducer, 0-10vdc, Installation guide, Wiring example

Advertising
background image

6%2)3

CURRENT MONITORING

INSTALLATION GUIDE

Z205456-0A

PAGE 1

©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / [email protected]

09083

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Solid-Core Current Transducer, 0-10VDC

Installer’s Specifications

Amperage Range

0-10/20/40 Amps (slide switch selectable)

Accuracy

±2% F.S. from 10% to 100% of selected range

Output

0-10VDC self-powered

Insulation Class

300VAC RMS

Frequency

50/60 Hz

Temperature Range

-15° to 60°C (-5° to 140°F)

Humidity Range

10-90% RH non-condensing

Safety

IEC 61010-1:2001 CAT III

For CE compliance, conductor shall be insulated accordint to IEC 61010-1:2001, Installation

Category III or equivalent.

The unit design provides for basic insulation only.

)";"3%0'&-&$53*$4)0$, &91-04*0/ 03"3$'-"4)

t 'PMMPXTBGFFMFDUSJDBMXPSLQSBDUJDFT

4FF/'1"&JOUIF64" PSBQQMJDBCMFMPDBMDPEFT

t 5IJTFRVJQNFOUNVTUPOMZCFJOTUBMMFEBOETFSWJDFECZRVBMJmFEFMFDUSJDBMQFSTPOOFM
t 3FBE VOEFSTUBOEBOEGPMMPXUIFJOTUSVDUJPOTCFGPSFJOTUBMMJOHUIJTQSPEVDU
t 5VSOPõBMMQPXFSTVQQMZJOHFRVJQNFOUCFGPSFXPSLJOHPOPSJOTJEFUIFFRVJQNFOU
t 6TFBQSPQFSMZSBUFEWPMUBHFTFOTJOHEFWJDFUPDPOmSNQPXFSJTPõ
 %0/05%&1&/%0/5)*4130%6$5'0370-5"(&*/%*$"5*0/
t 0OMZJOTUBMMUIJTQSPEVDUPOJOTVMBUFEDPOEVDUPST

'BJMVSFUPGPMMPXUIFTFJOTUSVDUJPOTXJMMSFTVMUJOEFBUIPSTFSJPVTJOKVSZ

%"/(&3

Wiring ExamplE

H723LC

723LC

DimEnsions

/05*$&

t 5IJTQSPEVDUJTOPUJOUFOEFEGPSMJGFPSTBGFUZBQQMJDBUJPOT

t %POPUJOTUBMMUIJTQSPEVDUJOIB[BSEPVTPSDMBTTJmFEMPDBUJPOT

t 5IFJOTUBMMFSJTSFTQPOTJCMFGPSDPOGPSNBODFUPBMMBQQMJDBCMFDPEFT

t .PVOUUIJTQSPEVDUJOTJEFBTVJUBCMFmSFBOEFMFDUSJDBMFODMPTVSF

quick install

Disconnect and lock out power.

1.

Install the mounting bracket to the back of the electrical enclosure, no closer than

2.

1/2” (12mm) to an uninsulated conductor.

Slide the conductor to be monitored through the sensing hole of the current

3.

switch. Terminate the conductor. See Notes (page 2) for currents under 1 Amp or
above 40 Amp.

Set the desired amperage range on the H723LC (10, 20, or 40 Amps).

4.

Wire the output connections between the H723LC and the controller (0-10VDC).

5.

Reconnect power.

6.

Scale the controller software to match the H723LC’s output.

7.

Fan or Pump

CONTACTOR

DDC CONTROLLER

AI

Motor

0.2” x 0.15”

slot (2x)

1.1"

(27 mm)

2.8"

(68 mm)

0.7" Dia

(19 mm)

0.9"

(23 mm)

3.0"

(75 mm)

Removable/Adjustable Mounting Bracket

3.8"

(95 mm)

4.2"

(106 mm)