hws calibration instructions
RH can be field calibrated by moving RUN/CAL jumper to CAL position.
1.
Relative humidity allows for calibration offset of ±9.9% RH – user discretion.
2.
O U T P U T
0 - 1 0 V
C A L
R H
+ 0 . 0
%
4 5 . 5 % R H
S E T P O I N T
4 5 % R H
SETPOINT MODE
(Enter by any keypress)
CONFIG/CAL MODE
(Run/cal jumper)
NORMAL MODE
only for switch in volts position
press± to change; press* to select
press± to change; press* to select
(choices are 50-95º F or 32-122º F)
in Cal Mode