POWER MONITORING

INSTALLATION GUIDE

ENERCEPT™ H8035/H8036

Networked Power Transducer (Modbus RTU)

US Patent No. 6,373,238

QUICK INSTALL

Disconnect and lock out power before installation.

1. Set the address switches located on the bottom of the CT.

2. Connect the voltage leads to the source to be monitored.

3. Snap the CT onto the conductor (observe color matching).

4. Connect the Modbus wires (observe polarity).

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and

operation of this electrical equipment and the installation, and has received safety

training to recognize and avoid the hazards involved.

NEC2009 Article 100

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

DANGER

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found

to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.

CAUTION

RISK OF EQUIPMENT DAMAGE

Enercept meters are rated for use at 50-60Hz. Do not connect this product to circuits with

high harmonic energy, such as Variable Speed Drives (a.k.a. Variable Frequency Drives,

Adjustable Frequency Drives) or similar sources, as these may permanently damage the

product.

Failure to follow these instructions can result in overheating and permanent

equipment damage.

For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must
control conductive pollution and the possibility of condensation or high humidity. Consider the
enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship
with the environment. Installation category: CAT II or CAT III

Installer’s Specifications

Measurement Accuracy:

System Accuracy

±1% of reading from 10% to 100% of the rated current*

Type of Measurement

One or three phase AC system

Input Voltage Characteristics:

Measured AC Voltage

208-480 VAC

Frequency Range

50/60 Hz

Fuses

1/2A, 600VAC, 200 kAIC

Input Current Characteristics:

Maximum Primary Current

100, 300, 400, 800, 1600, or 2400 A, continuous per phase**

Meter Current Draw:

Maximum

60 mA AC

Output:

Modbus RTU Protocol

RS-485, 2-wire plus common

Baud Rate 9600

Mechanical Conditions:

CT Case Isolation

600 VAC

Internal Isolation

2000 VAC RMS

Terminal Block Screw Torque

0.37 ft-lb (0.5 N·m) min.; 0.44 ft-lb (0.6 N·m) max.

Environmental Conditions:

Operating Temperature Range

2400 A model only: 0° to 50°C (32° to 122°F)

all

other models: 0° to 60°C (32° to 140°F)

Storage Temperature Range

-40° to 70°C (-40° to 158°F)

Operating Humidity Range

<95% RH non-condensing

Agency Approvals:

US and Canada (cULus)

UL508 (open type device)

* Meter accuracy specified with conductors centered in the CT window.

** For amperages greater than 2400A, see App Note VN19, www.veris.com/applicationnotes.aspx

TABLE OF CONTENTS

Quick Install

1

Operation

2

Product Identification

2

Dimensions

2

Product Diagram

2

Installation

3

Wiring

4

Data Outputs

4

Address Setup

5

Modbus Register Addressing

6

Using Integer Data Types

8

Notes

10

Troubleshooting

10