Installation guide, Network variable details – Veris Industries H8920-5 Install User Manual
Page 6

Z204057-0B
PAGE 6
©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
07111
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
H8920-5
INSTALLATION GUIDE
NETWORK VARIABLE DETAILS
Name
Type
Range
Description
nv1
nvoEgyWH
0-1e38kWH
kWh Consumption
nv2
nvoPower_f
0-1e38kW
kW Real Power
nv3
nviEgyClr
See text
Resets nvoEgykWH to zero
nv4
nviMeterIndex
1-63
Selects Modbus address
nv5
nvoMeterIndex
1-63
Reports selected Modbus address
nc49
nciMaxSendT
0.0-6553.4s
Maximum time between nvoPower updates. Default is 0 (disabled).
nc52
nciMinSendT
0.0-6553.4s
Minimum time between nvoPower updates. Default is 15 secs.
nc88
nciMinDelta
0.0-100%
Percent change in nvoPower that will force an nvoPower update. Default is 5%. Set to 0.0% to disable.
nc49
nciMaxSendTg
0.0-6553.4s
Maximum time between updates to all network variables. Default is 0 (disabled).