Veris Industries T SERIES Install User Manual

T series, Notice, Temperature transmitters

Advertising
background image

Z201986-0P

PAGE 1

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

05131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

ENVIRONMENTAL SENSORS

INSTALLATION GUIDE

Temperature Transmitters

SPECIFICATIONS

Input Power

4-20mA version: Loop powered 12-30VDC only, 30mA max;

0-5/0-10V versions: 12-30VDC/24VAC, 15mA max

Temp Output

2-wire loop powered 4-20mA or 3-wire 0-5V/0-10VDC

(switch

selectable in TWxA)

Sensor Type

Solid-state, integrated circuit (Transmitter)

Accuracy

±0.5°C (±1°F) typical

Ranges

0° to 50°C (32° to 122°F), -40° to 50°C (-40° to 122°F)

Wiring (TOA and TDDA)

22 AWG; 2-wire: 4-20mA;

3-wire:

Voltage output models

T SerieS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• Read and understand the instructions before installing

this product.

• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

No responsibility is assumed by Veris Industries for any consequences arising out of the

use of this material.

PRODUCT IDENTIFICATION

INSTALLATION

TDDA

1. Drill a hole in the duct.

2. Insert the temperature probe until the junction box is flat against the outer surface

of the duct.

3. Use screws to secure the junction box to the duct.

4. Wire as shown (see Wiring section).

TOA

1. Locate the sensor in an outside area, out of direct sunlight (e.g. under an eave,

north side of the building).

2. Mount the housing.

3. Wire as shown (see Wiring section).

TWxA

Observe precautions for handling static sensitive

devices to avoid damage to the circuitry that

is not covered under the factory warranty.

1. Mount the housing vertically on an interior wall in the area to be monitored, in

a location where air circulates freely. Locate unit away from air outlets, corners,
exterior walls, windows, and doors.

2. Wire as shown (see Wiring section).

TDDA

TOA

TWxA

TDDA

Output

M = 4-20mA
V = 0-5/10VDC

Cal Certificate

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

Range

1 = -40° to 50° C
(-40° to 122°F)
2 = 0° to 50°C
(32° to 122°F)

TOA

Cal Certificate

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

Range

1 = -40 to 50°C
(-40° to 122°F)
2 = 0° to 50°C
(32° to 122°F)

Output

M = 4-20mA
V = 0-5/10VDC

Sensor Type

TW

Local Display

= Transmitter
selectable
outputs

L = LCD
X = No

Setpoint/Override

Cal Certificate

0 = None
2 = 1k Setpoint
3 = 10k Setpoint
4 = 1k Setpoint with override
5 = 10k Setpoint with override

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

Housing Color

None = Cloud White
B = Black

A

PRODUCT OVERVIEW

The TDDA, TOA, and TWxA temperature sensors are equipped with a highly accuracy
temperature transmitter with analog output compatible with most building control
systems. To maintain accurate functionality, keep all vents free of dust, debris, etc.
These units are warranted for a period of five years.

Advertising