SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Response Time

1 sec.

Accuracy

±2% of full scale

Frequency Range

50/60 Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

LCD Backlight

Off at low currents; illuminates when monitored current exceeds 4.5A;

flashes during an alarm state while current remains above 4.5A

On-State Resistance

≤1.0 Ω

Off-State Resistance

≥1.0 MΩ

Setpoint Target Range, Switch Setting A*

±40% of learned nominal current; max. learned current of 142A to enable an upper trip limit at or below 200A

Setpoint Target Range, Switch Setting B*

±60% of learned nominal current;max. learned current of 125A to enable an upper trip limit at or below 200A

Switch Setting C*

On/Off Status; contacts are closed while amperage is above 2.5A

Alarm Reset Range

±5% of learned nominal current **

Setpoint Calibration Learn Period

30 sec.; self-learning, pushbutton reset

Normal-to-Alarm Output Delay

1 sec. maximum

Alarm-to-Normal Output Delay

30 sec. nominal

Insulation Class

600VAC RMS (UL); 300VAC RMS (CE)

Terminal Block Wire Size

24-14 AWG (0.2 to 2.1 mm

2

)

Terminal Block Torque

3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)

Agency Approvals

UL508 open device, CE: EN61010-1:2001-02, CAT III, pollution degree 2

* Trip point switch positions A and B are not for use in applications where the current will fluctuate by more than 40% (A) or 60% (B) of the nominal current. If the current will fluctuate by more than 60%, use the H11D for on/

off status (position C) only.

** The upper trip limit alarm resets when the current drops by 5% of the learned nominal current limit. The lower trip limit alarm resets when the current rises by 5% of learned nominal current limit.

Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2001.

The product design provides for basic insulation only.

Do not use the LCD as evidence of applied voltage.

DESCRIPTION

The Hawkeye TruStat H11D is a microprocessor based, self-learning, self-calibrating

current switch. It is designed for user ease, providing calibration-free status for

both under and overcurrent, an LCD display, and slide-switch selectable trip point

limits. At initial power-up, the H11D automatically learns the average current on the

line with no action required by the installer. Once a current is learned, the switch

monitors for changes in current greater than the selected range.

APPLICATIONS

●

HVAC fans, pumps, and blowers

●

Monitoring status of industrial process equipment

FEATURES

●

Backlit LCD display...view the monitored current (up to 200A)...eliminates the

need for expensive handheld meters and offers easy visibility in dark enclosures

●

Automatic calibration...reduced errors and installation costs

●

Slide-switch selectable trip point limits...application versatility

●

Microcontroller based learning technology...automatically learns load upon

initial power-up...eliminates labor associated with calibration

●

Records and displays the amperage level that trips the alarm...simplifies

troubleshooting

●

Reset function can be used when unpowered...reduces the possibility of an

undesirable arc flash incident

●

Monitors current for both under- and over-load in one package

●

100% solid state...no moving parts to fail

●

Small size fits easily inside small starter enclosures...saves space

●

Self-gripping iris for easy installation

●

Bracket can be installed in three different configurations...added flexibility

●

5-year warranty

LCD Display

Current Switch:

Auto Calibration,

Automation Systems

Maximize Reliability

Minimize Installed Cost

Year

Warranty

5

H11D

H11D

TM

LCD

DISPLA

Y!

LCD

DISPLA

Y!

HQ0003679.C 01131

Advertising