EnvironmEntal SEnSorS

inStallation GUiDE

Economy Wall Mount Humidity Sensor

HEW SEriES

HEW SEriES

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

Product IdentIfIcatIon

quIck Install

Observe precautions for handling static sensitive

devices to avoid damage to the circuitry that

is not covered under the factory warranty.

1. Mount the backplate on the wall in an appropriate location. Place so that the

“Install This End Up” statement on the board is in the upper right corner.

2. Wire the unit as shown (see Wiring section).

3. Attach the front plate.

Output

Temp.

Sensor Type

Accuracy

M = 4-20mA
V = 0-5V/0-10V

A = Temp Transmitter
B = 100R Platinum, RTD
C = 1k Platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor
K = 10k with 11k shunt, Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm TAC, Thermistor
R = 10k US, Thermistor
S = 10k 3A 221 Thermistor
T = 100k, Thermistor
U = 20k “D”, Thermistor
W = 10k T2 high accuracy, Thermistor
Y = 10k T3 high accuracy, Thermistor
Z = 10k E1, Thermistor

HEW

T = Temp
X = No Temp
(Stop here)

Installer’s Specifications

Input Power:

Input Power, Voltage Version

12-24 VDC or 24 VAC

Input Power, mA Version

12-24 VDC

AC Voltage Tolerance

±10%

AC Frequency

50-60 Hz

Max. Inrush Current After 1 msec (mA version)

25 mA

Output Power:

mA Output

4-20 mA, 2-wire, polarity insensitive

mA Max. Loop Resistance

500 Ω at 24 VDC input voltage; 250 Ω at 12 VDC input voltage

Voltage Output

0-5 V or 0-10 V (jumper selectable)

Voltage Min. Load Resistance

5 kΩ

Voltage Min. Sinking Current

0.2 mA

Humidity:

HS Element

Digitally profiled thin-film capacitive, non-removable

Accuracy

±2%, 3% or 5% (10-90% RH, 20° to 30°C (68° to 86°F))

Temperature Effect (Outside 20° to 30°C)

≤0.1% RH per °C

Response Time (to 90% change at 20°C)

110 sec

Annual Drift ≤1%

Output Scaling

0-100% RH

Temperature:

Active Output Accuracy

±0.5°C

Active Output Temperature Scaling

10° to 35°C (50° to 95°F)

Resistive Temperature Accuracy

see thermistor table

Self-Heating Error (Resistive Temperature Only)

≤±0.5°C at 20° to 30°C (68° to 86°F);

≤±0.75°C

outside of 20° to 30°C (68° to 86°F)

Operating Environment:

Operating Temperature

0° to 50°C (32° to 122°F)

Operating Humidity

0-100% RH (non-condensing) (Unit will recover from saturation)

Housing:

Material

ABS plastic with UL V-0, 5VB Flame Class

Mounting Holes

US and European junction box

EMC Conformance: EN61000-6-3:2007+A1:2011 Class B, EN61326-1:2006 Class B; EN61000-6-

1:2007

1-year limited warranty.

S

= Standard

Temp Cert

Blank = None
1 = 1 pt cal
2 = 2 pt cal

RoHS

Compliant

2 = 2%
3 = 3%
5 = 5%