Veris Industries HW SerieS Datasheet User Manual

Deluxe wall humidity sensors, Hw series, Hu midit y

Advertising
background image

HU
MIDIT

Y

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

1% & 2% NIST, or Standard

2%, 3%, or 5%

HWL

Deluxe Wall Humidity Sensors

DESCRIPTION

HW Deluxe humidity transmitters provide an ideal solution for measuring relative
humidity in all conditions. All devices are equipped with a thin-film capacitive
sensor that is easily replaceable in the field. These sensors are calibrated to NIST
standards, with certificates available (see Ordering Information; choose “N” in NIST
block). Temperature sensing options are also available.

The wall-mounted HW model features a low-profile housing with an optional
LCD display for easy visibility. All Deluxe models come with a standard five-year
warranty.

APPLICATIONS

Controlling HVAC systems for improved comfort and energy savings

Museums, schools, printing shops, and other locations requiring humidity

control

Facilitating compliance with ASHRAE standards for environmental control and

indoor air quality

FEATURES

Thin-film capacitive sensor element recovers from 100% saturation

Fully interchangeable element to 1%, 2%, 3%, or 5% accuracy...no calibration

Replace element in the field...maintain accuracy and minimize downtime

Polarity insensitive, two-wire 4-20 mA or 3-wire 0-5/0-10 VDC versions...

flexible systems compatibity...save time in the field and stock fewer devices

Calibration-free interchangeable NIST traceable HS element

HS element is microprocessor profiled with on-board nonvolatile memory

Multi-point digital calibration to NIST standards

NIST certification available

Minimizes field calibration downtime

SPECIFICATIONS

HS Element

Digitally profiled thin-film capacitive (32 bit mathematics) U.S. Patent 5,844,138†

Accuracy at 25°C from 10-80% RH*

±2%, 3%, or 5% models; ±1% at 12-60% RH in voltage output mode; ±1% at 12-60% RH in mA output mode with temp transmitter;

±1% at 20-40% RH in mA output mode; (multi-point calibration, NIST traceable)

Reset Rate**

24 hours

Stability

±1%@20°C (68°F) annually, for two years

Operating Humidity Range

0 to 100% RH noncondensing

Hysteresis

1.5% typical

Linearity

Included in accuracy spec.

Temperature Coefficient

±0.1% RH/°C above or below 25°C (typical)

Analog Output

4-20mA mode: 2-wire, not polarity sensitive (clipped and capped); 0-5V/0-10V mode: 3-wire, observe polarity

Scaling

0-100% RH

Operating Temperature Range

10° to 35°C (50° to 95°F)

Input Power***

4-20 mA mode: loop powered 12-30VDC only, 30mA max.; 0-5V/0-10V mode: 12-30VDC/24VAC, 15mA max.

Optional Temperature Transmitter Output

Digital, 4-20mA (clipped and capped) or 0-5V/0-10V output; accuracy ±0.5°C (±1°F) typical

10° to 35°C (50° to 95°F and 0° to 50°C (32° to 122°F) (switchable)

† The HS sensing element has a 1-year warranty. The element is not a part of the 5-year product warranty.

* Specified accuracy with 24VDC supplied power with rising humidity. RTD/Thermistors are not compensated for internal heating of product.

** Reset Rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.

*** One side of transformer secondary is connected to signal common, so an Isolation transformer or dedicated power supply may be required.

Shielded cabling is required for conformance to EMC standards. Technical information is available from factory upon request or is available on our website: www.veris.com.