Pressure, Application/wiring diagram dimensional drawing, Accessories – Veris Industries PH SERIES Datasheet User Manual
Page 2: Ordering information, Signal conditioning diagram

pressure
800.354.8556
+1 503.598.4564
www.veris.com
APPLICATION/WIRING DIAGRAM
DIMENSIONAL DRAWING
1/4” NPT male thread,
17-4 PH stainless
NIST
N = NIST
X = None
Range
07 = 0-100 psig
08 = 0-250 psig
09 = 0-500 psig
10 = 0-1000 psig
PH S
Example:
PH X 07 S
ACCESSORIES
Snubbers (AA11), steam siphon (AA13)
= Standard
ORDERING INFORMATION
MODEL
07
08
09
10
A
25
62.5
125
250
B
50
125
250
500
C
100
250
500
1000
RANGE
+
-
-
POWER SOURCE
12 to 30 VDC/24 VAC
DIGITAL CONTROL
Analog Input
0-5V/0-10V
or 4-20mA
Optional
Digital Output
VIN
OUT
COMMON
Zero
Remote
Zero
Slow
Fast
VOLT
mA
0-5
0-10
Response
Output
Range
TEST
A
B
C
2.25"
(57 mm)
2.2"
(56 mm)
4.5"
(115 mm)
5.1"
(129 mm)
2.5"
(62 mm)
AA11
AA13
0
Actual Pressure
Digitally Conditioned Output
TIME
F.S.
PRESSURE
Noise Rejection
Surge Damping
Output Clamping
SIGNAL CONDITIONING DIAGRAM
HQ0001825.B 01131