Veris Industries H701 Datasheet User Manual

Current switches: adjustable trip point, Current monit oring

Advertising
background image

current monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Detect Belt Loss, Coupling

Shear, And Mechanical Failure

H308

Year

Warranty

5

FEATURES

●

High performance devices in split- and solid-core housings

●

Adjustable trip point...precise current trip point setting

●

Minimum trip point as low as 0.5A (H608)...eliminates the need for multiple

wraps of the conductor through the sensor even on loads as small as 1/5 HP

●

Small size...fits easily inside small enclosures

●

Self-gripping iris on the split-core housing for easy installation

●

Status LEDs available for easy setup and local indication

●

Bracket on H908 can be installed in three different configurations...installation

flexibility in tight spaces

●

1 Amp status output...increased application flexibility

●

All devices are 100% solid state for high reliability and polarity insensitive for

trouble-free installation, with a 5-year warranty

DESCRIPTION

Hx08 Series and H701 adjustable current switches offer high performance, with

a wide array of amperage range options. These products can accurately detect belt

loss, coupling shear, or other mechanical failure on loads from 1/5 to 100 HP.

APPLICATIONS

●

Detecting belt loss, coupling shear, and mechanical failure

●

Verifying lighting circuit and other electrical service run times

●

Monitoring status of industrial process equipment

●

Monitoring status of critical motors (compressor, fuel, etc.)

SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Insulation Class

600VAC RMS (UL), 300VAC RMS (CE)

Frequency Range

50/60 Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH, non-condensing

Hysteresis

10% (typical)

Terminal Block Wire Size

H608, H701, H708, H808, H908: 24-14 AWG (0.2 to 2.1 mm

2

); H308: 22-16 AWG (0.3 to 1.3 mm

2

)

Terminal Block Torque

H608, H701, H708, H808, H908: 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m); H308: 7 in-lbs (0.8 N-m)

Agency Approvals

UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation

Do not use the LED status indicators as evidence of applied voltage.

H808

H708

H608

H908

Current Switches:

Adjustable Trip Point

Maximize Reliability

Minimize Installed Cost

Hx08 SERIES & H701

TM

DETECTS BELT LOSS/COUPLING SHEAR!

DETECTS BELT LOSS/COUPLING SHEAR!

Now you can easily detect when drive belts slip, break, or pump couplings shear.

In fact, a typical HVAC motor that loses its load has a reduction of current draw

of up to 50%. That’s why our sensors are the industry standard for status.

Calibrated

Trip Point

Off

Off

Fan/pump

On

Loss of Belt/Coupling Shear

Electrical

Failure

HQ0001754.B 01131

Advertising