Veris Industries H701 Datasheet User Manual

Current switches: adjustable trip point, Current monit oring

Advertising
background image

current monit

oring

VERIS INDUSTRIES

800.354.8556

+1 503.598.4564

www.veris.com

Detect Belt Loss, Coupling

Shear, And Mechanical Failure

H308

Year

Warranty

5

FEATURES

High performance devices in split- and solid-core housings

Adjustable trip point...precise current trip point setting

Minimum trip point as low as 0.5A (H608)...eliminates the need for multiple

wraps of the conductor through the sensor even on loads as small as 1/5 HP

Small size...fits easily inside small enclosures

Self-gripping iris on the split-core housing for easy installation

Status LEDs available for easy setup and local indication

Bracket on H908 can be installed in three different configurations...installation

flexibility in tight spaces

1 Amp status output...increased application flexibility

All devices are 100% solid state for high reliability and polarity insensitive for

trouble-free installation, with a 5-year warranty

DESCRIPTION

Hx08 Series and H701 adjustable current switches offer high performance, with

a wide array of amperage range options. These products can accurately detect belt

loss, coupling shear, or other mechanical failure on loads from 1/5 to 100 HP.

APPLICATIONS

Detecting belt loss, coupling shear, and mechanical failure

Verifying lighting circuit and other electrical service run times

Monitoring status of industrial process equipment

Monitoring status of critical motors (compressor, fuel, etc.)

SPECIFICATIONS

Sensor Power

Induced from monitored conductor

Insulation Class

600VAC RMS (UL), 300VAC RMS (CE)

Frequency Range

50/60 Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH, non-condensing

Hysteresis

10% (typical)

Terminal Block Wire Size

H608, H701, H708, H808, H908: 24-14 AWG (0.2 to 2.1 mm

2

); H308: 22-16 AWG (0.3 to 1.3 mm

2

)

Terminal Block Torque

H608, H701, H708, H808, H908: 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m); H308: 7 in-lbs (0.8 N-m)

Agency Approvals

UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation

Do not use the LED status indicators as evidence of applied voltage.

H808

H708

H608

H908

Current Switches:

Adjustable Trip Point

Maximize Reliability

Minimize Installed Cost

Hx08 SERIES & H701

TM

DETECTS BELT LOSS/COUPLING SHEAR!

DETECTS BELT LOSS/COUPLING SHEAR!

Now you can easily detect when drive belts slip, break, or pump couplings shear.

In fact, a typical HVAC motor that loses its load has a reduction of current draw

of up to 50%. That’s why our sensors are the industry standard for status.

Calibrated

Trip Point

Off

Off

Fan/pump

On

Loss of Belt/Coupling Shear

Electrical

Failure

HQ0001754.B 01131

Advertising