Enclosed Victory Relays:

10A SPDT

DESCRIPTION

Victory 100 and 200 Series 10A enclosed relays are pilot-duty relays in an easy-
to-use nipple mount enclosure. The V100/V200 Series provide quick relay mounting
without a dedicated field enclosure, making them ideal for retrofit projects. Field-
selectable high and low voltage coil inputs provide on-site versatility.

APPLICATIONS

●

Command contactors

●

Control motors

●

Isolation

●

Device interlocking

●

Relay logic

●

Sense voltages for alarm conditions

FEATURES

●

Sleek field enclosure reduces the need for panel space

●

The nipple mount feature allows the Victory Series to be mounted to any

electrical enclosure

●

Flexible tinned stranded wire...fits easily in tight spaces & provides secure

connections to wire nuts

●

UL508 Listed...designed and approved for field installation...makes electrical

inspection a snap

●

Run low voltage instead of line voltage...eliminate conduit in some applications

SPECIFICATIONS

Operating Temperature Range:

V100, V100DC, V200

-34° to 60°C (-29° to 140°F)

V100D, V200D

-40° to 55°C (-40° to 131°F)

Operating Humidity Range

10-90% RH non-condensing

Expected Relay Life

Electrical (@ rated current) 100,000 cycles; Mechanical (unpowered) 10,000,000 cycles

Relay Status

LED ON=energized

Wire Specifications:

Lead Length

14” (356 mm) min.

Gauge

UL1015; Coil: 18 AWG; Contacts: 16 AWG

Insulation Class

600VAC RMS

Agency Approvals

UL 508

Great For External

Mount Applications

Pull in Voltage

AC

DC

10-30V..................................... 8

9

120V........................................ 78

208-277V................................. 154
Drop Out Voltage

AC

DC

10-30V..................................... 2 3

120V........................................ 18

208-277V................................ 36
Voltage

Coil Current

AC DC

10V.......................................... 25mA 14mA

12V.......................................... 25mA 14mA

24V.......................................... 31mA 16mA

30V.......................................... 39mA 18mA

120V........................................ 22mA

-

208V........................................ 19mA

277V........................................ 25mA

TYPICAL COIL PERFORMANCE

CONTACT RATINGS

Resistive.............. 10A@277VAC, 28VDC
Motor.................... 120VAC, 1/3HP N.O. & 1/6HP N.C.

240VAC, 1/3HP N.O. & 1/6HP N.C.

277VAC, 1/4HP N.O. & 1/8HP N.C.

Pilot Duty............. 277VAC, (1.7A), 480VA N.O.
Ballast.................. 277VAC, 1.7A
Tungsten............... 120VAC, TV3 N.O. TV2 N.C.
Gold Flash............. Yes

Year

Warranty

5

V100

V200D

VICTORY 100 & 200 SERIES

Year

Warranty

5

HQ0001833.B 01131